Goodrive20 Series VFD
Function parameter list
-96-
Function
code
Name
Description
Default Modify
Setting range of
P11.08
:
The function code is used to enable and
define
the
overload
pre-alarm
of
the
VFD/motor.
Setting range: 0x0000
–0x1132
Ones place:
0: Motor overload/underload pre-alarm,
relative to rated motor current;
1: VFD overload/underload pre-alarm, relative
to rated VFD current.
2: Motor output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0: The VFD continues running after
overload/underload alarm;
1: The VFD continues running after underload
alarm, and stops running after overload fault;
2: The VFD continues running after overload
alarm, and stops running after underload fault;
3: The VFD stops running after
overload/underload fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: Overload integral function
selection
0: Overload integral is invalid;
1: Overload integral is valid.
Setting range of
P11.09
:
P11.11
–200%
(
relative value determined by ones place of
P11.08)
Setting range of
P11.10
: 0.1
–3600.0s
P11.11
Underload
pre-alarm
detection
level
Underload pre-alarm signal will be outputted if
the output current of the VFD or motor is lower
than underload pre-alarm detection level
(
P11.11
), and the duration exceeds underload
pre-alarm detection time (
P11.12
).
Setting range of
P11.11
: 0
–
P11.09
(relative
value determined by ones place of P11.08)
50%
○
P11.12
Underload
pre-alarm
detection
1.0s
○