Goodrive20 Series VFD
Function parameter list
-99-
Function
code
Name
Description
Default Modify
0: No check (N, 8, 1) for RTU
1: Even check (E, 8, 1) for RTU
2: Odd check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even check (E, 8, 2) for RTU
5: Odd check (O, 8, 2) for RTU
6: No check (N, 7, 1) for ASCII
7: Even check (E, 7, 1) for ASCII
8: Odd check (O, 7, 1) for ASCII
9: No check (N, 7, 2) for ASCII
10: Even check (E, 7, 2) for ASCII
11: Odd check (O, 7, 2) for ASCII
12: No check (N, 8, 1) for ASCII
13: Even check (E, 8, 1) for ASCII
14: Odd check (O, 8, 1) for ASCII
15: No check (N, 8, 2) for ASCII
16: Even check (E, 8, 2) for ASCII
17: Odd check (O, 8, 2) for ASCII
P14.03
Communicatio
n response
delay
0
–200ms
The
function
code
indicates
the
communication response delay, that is,
the interval from when the VFD completes
receiving data to when it sends response
data to the upper computer. If the
response delay is shorter than the VFD
processing time, the VFD sends response
data to the upper computer after
processing data. If the delay is longer than
the VFD processing time, the VFD does
not send response data to the upper
computer until the delay is reached
although data has been processed.
5
○
P14.04
Communicatio
n overtime
fault time
0.0 (invalid), 0.1
–60.0s
When the function code is set to 0.0, the
communication timeout time is invalid.
When the function code is set a non-zero
value, the rectifier reports the "485
communication
fault"
(CE)
if
the
communication interval exceeds the value.
0.0s
○