OF-500 OptiFiber Certifying OTDR
Technical Reference Handbook
B-6
3 Jumper Method
Results from the 3 Jumper method account for the loss of
only the fiber in the link. This method is suitable for testing
links where the fiber's loss is the majority of the total loss,
such as when the link is very long or patch cords are not
used at either end. Appendix A shows the names of the
standards that define the 3 Jumper method.
Reference connections for the 3 Jumper method cancel out
the effects of two connections and three reference test
cords in each fiber path, as shown in Figure B-3.
The test connections add the fiber in the link to each path.
Loss results for the 3 Jumper method therefore represent
only the fiber in the link.
Because the results omit both connections in the link,
industry standards do not recommend the 3 Jumper
method for testing premises fiber, where patch cords are
typically used at both ends of the link and connector loss is
a large portion of the total loss.
Summary of Contents for OF-500-01 OptiFiber
Page 4: ......
Page 18: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook xiv...
Page 29: ...Getting Acquainted Powering the Tester 1 9 1 ajt20f eps Figure 1 1 Battery Pack Feature...
Page 31: ...Getting Acquainted Verifying Operation 1 11 1 ajt56f eps Figure 1 2 Removing the Module...
Page 48: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 1 28...
Page 76: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 2 28...
Page 110: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 3 34...
Page 132: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 3 56...
Page 138: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 4 6...
Page 144: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 5 6...
Page 196: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 7 44...
Page 216: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 10 10...
Page 254: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook 12 30...
Page 256: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook A 2...
Page 268: ...OF 500 OptiFiber Certifying OTDR Technical Reference Handbook C 2...