Generator Faults
Seite/Page 192 - Kaptitel/Chapter 10: Generator Faults
9.12.14
10.4 Defective fuel pump.
Get the fuel pump exchanged at a Fischer Panda Service point/Service Centre.
10.5 Buckled fuel hose.
Arrange the fuel hose in a way that no buckles can form.
10.6 Leaky connections/pipes.
Seal the connections professionally - Exchange leaky pipes.
11.1 Actuator arbor is jammed.
Check the Max/Min-adjustments and grease the actuator arbor, as described in the chapter Generator Faults’.
11.2 Connection assembly actuator disrupted.
Rebuild connection assembly.
11.3 Defective DC fuse on the VCS.
Get the relevant fuses exchanged at a Fischer Panda Service point/Service Centre.
The exchange is described in the chapter Generator Faults’.
A defective fuse is not always visually detectable. Measure the fuse with a multimeter for connecting passage.
Attention: Voltage up to 400V - Danger to life!
The operations are to be executed by a trained
professional only!
11.4 Disrupted measuring voltage to VCS.
Get the measuring voltage cable connected/exchanged by a Fischer Panda Service point/Service Centre.
Attention: Voltage up to 400V - Danger to life!
The operations are to be executed by a trained professional
only!
.
11.5 Generator is overloaded.
Reduce the load. Ensure that the generator does not get overloaded.
12.1 Air in the fuel system.
See 10.1
12.2 Lack of fuel
Re-assemble the fuel supply.
12.3 Faults in the redundant temperature circuit.
Get the temperature switch as well as the connection assemble and electric cables checked and repaired by a
Fischer Panda Service point/Service Centre
12.4 Generator is overloaded.
See11.5
13.1 Lack of cooling water.
Refill the cooling water as described in the chapter Maintenance’.
13.2 Defective impeller pump.
Replace the defective impeller as described in the chapter Maintenance’.
13.3 Air in the cooling system.
Ventilate the cooling system as described in the chapter Maintenance’.