A. Technical appendix
A-11
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
Index
(hex)
Explanation
Values
(hex)
Map.
Attr.
Type
Designa-
tion
Sub-
index
1800
0
Transmit
PDO Com-
munication
Mapping
Parameter 0
U8
ro
–
05
Input PDO 0 Communication
Parameter
1
COB-ID
U32
rw
180 + Node ID
Default COB-ID of the
inputs
2
Transmis-
sion type
U8
FF
Default: acyclic
3
Inhibit Time
U16
00 00
Transmit blocking time
inputs
5
Event Timer
0
Time-controlled transmis-
sion of the inputs [ms]
1801
0
Transmit
PDO Com-
munication
Mapping
Parameter 1
U8
ro
–
05
Input PDO 1 Communication
Parameter
1
COB-ID
U32
rw
280 + Node ID
Default COB-ID of the
inputs
2
Transmis-
sion type
U8
FF
Default: acyclic
3
Inhibit Time
U16
00 00
Transmit blocking time
inputs
5
Event Timer
0
Time-controlled transmis-
sion of the inputs [ms]
Summary of Contents for CTEU-CO
Page 2: ......
Page 14: ...Installation XII Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 15: ...Commissioning 1 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 1 Commissioning ...
Page 37: ...Diagnosis 2 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 2 Diagnosis ...
Page 51: ...Error treatment 3 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 3 Error treatment ...
Page 58: ...3 Error treatment 3 8 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 59: ...Technical appendix A 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix A Technical appendix ...
Page 74: ...A Technical appendix A 16 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 75: ...Index B 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix B Index ...
Page 76: ...B Index B 2 Festo P BE CTEU CO OP MAINT EN en 1101NH Contents B Index B 1 ...