2. Diagnosis
2-10
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
The pre-defined error field as fault memory
If the Emergency Message is transmitted, a compressed form
of the fault information will be saved parallel in the Pre-Defined
Error Field (Index 1003).
Device 1 + 2 DIAG, Error Code
The Pre-defined Error Field serves as fault memory for the last
faults ascertained.
Error Codes
Note
If several Emergency Messages from Tab. 2/7 are present,
only the most recently reported is transmitted to the mas-
ter controller.
Byte 0
Byte 1
Explanation
00
00
No error
20
22
Short circuit diagnostics
20
23
Short circuit at outputs
20
31
Operating voltage too low
20
33
Load voltage too low
00
50
Hardware fault
30
81
Node guarding or Heartbeat error
00
FF
Configuration error
FF
FF
Diagnostic message from I-Port telegram
Tab. 2/7:
Bus node Error Codes (as per DS401)
Summary of Contents for CTEU-CO
Page 2: ......
Page 14: ...Installation XII Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 15: ...Commissioning 1 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 1 Commissioning ...
Page 37: ...Diagnosis 2 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 2 Diagnosis ...
Page 51: ...Error treatment 3 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 3 Error treatment ...
Page 58: ...3 Error treatment 3 8 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 59: ...Technical appendix A 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix A Technical appendix ...
Page 74: ...A Technical appendix A 16 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 75: ...Index B 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix B Index ...
Page 76: ...B Index B 2 Festo P BE CTEU CO OP MAINT EN en 1101NH Contents B Index B 1 ...