1. Commissioning
1-8
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
1.3.2
Rules for internal I/O mapping
The following rules are applied when using the PDOs:
–
The telegrams are filled in ascending order.
–
Mapping can be used individually via both PDOs.
–
The inputs and outputs are factory-arranged according to
the standard mapping function.
–
The I/Os are arranged according to the standard mapping
function when a device is connected and the bus node is
switched on.
–
Process data allocation between the bus node and valve
terminal remains in effect even if the two modules are
separated, provided that the bus node remains under
voltage during the separation. Otherwise the mapping
information of connected devices is deleted.
1.3.3
I/O linking by COB-IDs
COB-IDs are made up of the function code (see Tab. 1/3) and
the address of the respective fieldbus station (Node ID):
10
9
8
7
6
5
4
3
2
1
0
Function Code
Node ID
Tab. 1/2:
Configuration of COB-IDs
Summary of Contents for CTEU-CO
Page 2: ......
Page 14: ...Installation XII Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 15: ...Commissioning 1 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 1 Commissioning ...
Page 37: ...Diagnosis 2 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 2 Diagnosis ...
Page 51: ...Error treatment 3 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 3 Error treatment ...
Page 58: ...3 Error treatment 3 8 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 59: ...Technical appendix A 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix A Technical appendix ...
Page 74: ...A Technical appendix A 16 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 75: ...Index B 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix B Index ...
Page 76: ...B Index B 2 Festo P BE CTEU CO OP MAINT EN en 1101NH Contents B Index B 1 ...