2. Diagnosis
2-11
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
Error register
Note
One or more Error Codes for each Emergency Message can
be transferred to the master controller with the help of the
Emergency Messages from Tab. 2/8.
Bit
Meaning
Explanation
0
Generic error
Bit is set for each error
1
Current
– Short circuit/overload of sensor supply
– Short circuit/overload of connected devices
2
Voltage
– Operating voltage too low
– Load voltage too low
– Load voltage not applied
3
–
–
4
Communication
Error
– Node guarding, Heartbeat, CANopen error
5 … 6
–
–
7
Manufacturer
specific
– Wire fracture
– other errors
Tab. 2/8:
Error Register (Object 1001 with bit assignment as per DS301/401)
Manufacturer Status Register
Error causes of the devices connected to the bus node are
transmitted via bytes 3 and 4 or 5 and 6 of the Emergency
Message (Manufacturer Status Register, Object 1002).
Transmittable error causes
The following error causes are reported to the master control-
ler by the bus node (Tab. 2/9):
Summary of Contents for CTEU-CO
Page 2: ......
Page 14: ...Installation XII Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 15: ...Commissioning 1 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 1 Commissioning ...
Page 37: ...Diagnosis 2 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 2 Diagnosis ...
Page 51: ...Error treatment 3 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Chapter 3 Error treatment ...
Page 58: ...3 Error treatment 3 8 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 59: ...Technical appendix A 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix A Technical appendix ...
Page 74: ...A Technical appendix A 16 Festo P BE CTEU CO OP MAINT EN en 1101NH ...
Page 75: ...Index B 1 Festo P BE CTEU CO OP MAINT EN en 1101NH Appendix B Index ...
Page 76: ...B Index B 2 Festo P BE CTEU CO OP MAINT EN en 1101NH Contents B Index B 1 ...