4
Commissioning
Festo – P.BE-CPX-CTEL-EN – 1601b – English
35
4.6.4
Parameter “Behaviour after I-Port short circuit”
Through the parameter “Behaviour after I-Port short circuit”, the status of the load voltage supply can
be established for an I-Port device after elimination of a short circuit in an I-Port connecting cable.
After the short circuit is eliminated, the power supply for the corresponding device can
–
remain switched off (setting “Leave switched-off ”) or
–
be automatically switched on again (setting “switch on again”).
The parameter “Behaviour after I-Port short circuit” is embedded as bit 7 in parameter 8.
The remaining 7 bits are assigned otherwise (
è
When the parameter for changing of the setting is overwritten, the content of the bits
6 … 0 can be any desired. Only bit 7 is evaluated for parameterisation.
With access via FMT or MMI, the parameter can be selected and changed separately. In this way,
the parameters “I/O mode” and “I/O length” can only be read.
Parameter information
The setting is conducted via bit 7 of parameter 8 (relative address 7).
Bit 7
Parameter setting
0
Leave switched off (default setting)
1
Switch on again
Tab. 4.2
4.6.5
Parameter “Device parameter I-Port”
For each connected device, 8 bytes are available for representation of the device parameters. These
parameters are individually interpreted by each device and are defined in the description of the corres
ponding device.