A
Commissioning
52
Festo – P.BE-CPX-CTEL-EN – 1601b – English
CTEL system
Design
Protocol
I-Port
Number of I-Port interfaces
4
Maximum number of devices per I-Port
1
Maximum cable length per I-Port
[m]
20
Number of inputs/outputs for module
[byte]
32 I/32 O
Transmission rate (per I-Port)
[kbps]
230.4
Internal cycle time (dependent on
the connected devices)
[ms]
1 per 1 byte of user data parallel each
connected device
Electrical connection
4 × sockets M12, 5-pin, A-coded
LED indicators
Status system supply
Status load voltage
I-Port status/diagnostics
Module status
Maximum cable length between module
and device
[m]
20
Short-circuit protection
Supply for devices (PS) and load voltage (PL)
Internal (electronic), separate for each
I-Port
Behaviour after short circuit
Dependent on parameter “Behaviour
after short circuit”
Reverse polarity protection
Separate for each system and load
voltage, not separated per I-Port
Parameterisation
Module parameter
Diagnostic behaviour
Fail safe (per channel)
Forcing (per channel)
Idle mode (per channel)
Diagnostics
Module-oriented diagnostics
Undervoltage PS
Undervoltage/short circuit of modules
Undervoltage PL (over device)
I-Port
Communication error
Short-circuit PS/PL
Device error
Undervoltage identification PS
Trigger level
[V]
approx. 17.5
Hysteresis
[mV]
approx. 500
1)
Measurement takes place in CTEL master module
Tab. A.3
Summary of Contents for CPX-CTEL-4-M12-5POL