A
Commissioning
Festo – P.BE-CPX-CTEL-EN – 1601b – English
53
A.2
Event codes
Within the I-Port communication between the CTEL master module and the devices, so-called events
are used for status diagnostics, which include an error code (event code), each with a constant length
of 2 bytes. The following table provides an overview of the event codes with the corresponding error
description.
Information regarding error handling can be found in Tab. 5.3.
Event
code
Error instance
Description
CPX error no.
---
Internal
Short circuit at I-Port supply (PS/PL) or communica
tion signal
56
---
I-Port configuration error
58
---
I-Port device missing/failed
57
---
Invalid parameters received from the host system
(parameterisation error)
29
0x…
I-Port device
All other event codes not specified in this table
1
0x0000
Device OK
0
0x1000
Device NOK, general diagnostics
1
0x4000
Temperature overload
0x4210
Device has exceeded temperature limit
10
0x4220
Device has fallen below temperature limit
9
0x5000
Hardware error – device replacement
1
0x5010
Component error – repair or replacement
0x5011
Error in memory buffering
9
0x5012
Low battery level
0x5100
General error in power supply
1
0x5101
Fuse triggered
0x5110
Primary voltage/main power supply too low
10
0x5111
Primary voltage/main power supply too low
5
0x5112
Undervoltage PL device (only relevant if PL monitoring
is active in a device)
0x6000
Device software error
1
0x6320
Parameter error
29
0x6321
Missing parameters
0x6350
Changed parameter
Summary of Contents for CPX-CTEL-4-M12-5POL