4
Commissioning
Festo – P.BE-CPX-CTEL-EN – 1601b – English
33
Relative
Address
Mod. par.
Module parameter
Bit
R/W
Relative
Address
Mod. par.
Module parameter
0
1
2
3
4
5
6
7
R/W
8 … 15
RW
8 bytes (hexadecimal, subdivided word by word)
Device parameter I-Port 1
16 … 23
RW
8 bytes (hexadecimal, subdivided word by word)
Device parameter I-Port 2
24 … 31
RW
8 bytes (hexadecimal, subdivided word by word)
Device parameter I-Port 3
32 … 39
RW
8 bytes (hexadecimal, subdivided word by word)
Device parameter I-Port 4
40 … 43
R
32-bit (hexadecimal)
Device type I-Port 1
44 … 47
R
32-bit (hexadecimal)
Device type I-Port 2
48 … 51
R
32-bit (hexadecimal)
Device type I-Port 3
52 … 55
R
32-bit (hexadecimal)
Device type I-Port 4
56+57
58+59
60+61
62+63
R
16-bit (hexadecimal)
16-bit (hexadecimal)
16-bit (hexadecimal)
16-bit (hexadecimal)
Device error code I-Port 1
Device error code I-Port 2
Device error code I-Port 3
Device error code I-Port 4
1)
These parameters are read out only during initialisation of the CTEL master module. Subsequent changes of the parameters have
no effects. Bits 0 ... 3 cannot be written in combination with the Festo Maintenance Tool and the operator unit. They are represen
ted in the online mode as read-only parameters.
2)
with fixed length
Tab. 4.1
4.6.2
Parameter “Monitoring U
OUT
/U
VAL
”
Monitoring of the load voltage U
OUT
or U
VAL
, which is activated as standard, can be deactivated via
the parameter “Monitoring U
OUT
/U
VAL
”.
When monitoring is deactivated, any undervoltage that then occurs is ignored. If the CTEL master mod
ule already reports an undervoltage (related to U
OUT
/U
VAL
), this message is deleted when this paramet
er is set to “inactive”.
Setting of this parameter applies for the entire module, that is, for all I-Ports equally.
4.6.3
Parameter “I-Port configuration”
Through the parameter “I-Port X configuration” (X = number of the I-Port), the type of diagnostics or
error control can be established for each I-Port.
First and foremost, the setting is used for monitoring whether a device is connected and, if so, whether
it fits the configuration presetting.
At system start, the parameter is set to “Use existing device”. This setting can only be
changed after the system start.
Summary of Contents for CPX-CTEL-4-M12-5POL