SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-
Default
Type
Read Only
Trip Code Descriptions
Internal Unit Failure
2201-2299 2701-2799
MPU Trip
The Unit has failed internally and is unable to recover automatically.
Cycle the control supply.
If the fault is not cleared then contact the supplier
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
The input phase rotation is RBY (L1-L3-L2)
2102
Rotation L1 L3 L2 Trip
The phase rotation is opposite to that required.
Change phase rotation or if "RBY" trip is not required turn "off" in trip settings.
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
The input phase rotation is RYB (L1-L2-L3)
2101
Rotation L1 L2 L3 Trip
The phase rotation is opposite to that required.
Change phase rotation or if "RYB" trip is not required turn "off" in trip settings.
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
The remote start signal is active.
2001-2003
Remote Start is Enabled
The remote start signal was active during power up or Reset or Parameter Load.
Turn off remote or if Remote On trip is not required turn "off" in "Trip Settings"
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
The Unit cover is open
1901
Cover Open, Close to Enable Motor Start
The cover is open or not closed properly
Close Cover or if Cover trip is not required turn off in "Trip Settings"
The Trip Number shown in PNU Name is a
decimal value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016