SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0%
-
16384 ( 4000 hex ) 100%
Default
0 ( 0 hex ) 0%
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) On
Type
Read/Write
53762 ( D202 hex )
Detects if there is a disconnection between the Unit input and the supply when the motor is running.
Input Side Phase Loss
On : Trips if there is a disconnection between the input side of the Unit and the supply when the motor is running.
8 bit unsigned
Off : The Unit will attempt to run although the operation may be erratic.
Operating in this mode for prolonged periods may result in SCR failure
Binary value
44864 ( AF40 hex )
Adjusts the reaction time to fault trips
Trip Sensitivity
Increase "Trip Sensitivity" to slow the response to fault trips.
Sometimes useful on sites were electrical noise is causing nuisance tripping
16 bit unsigned
This is a global setting.
Increasing "Trip Sensitivity" will slow the response of all the trips.
Linear Scaling ( 1 = 0.006104 % )
40329 ( 9D89 hex )
Displays the overload level at the end of the last successful start -9
Last overload-9
16 bit unsigned
Linear Scaling ( 1 = 0.006104 % )
40328 ( 9D88 hex )
Displays the overload level at the end of the last successful start -8
Last overload-8
16 bit unsigned
Linear Scaling ( 1 = 0.006104 % )
40327 ( 9D87 hex )
Displays the overload level at the end of the last successful start -7
Last overload-7
16 bit unsigned
Linear Scaling ( 1 = 0.006104 % )
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 43 of 59