SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
-hh:mm:ss
-
-hh:mm:ss
Default
GMT timehh:mm:ss
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-hh:mm:ss
-
-hh:mm:ss
Default
GMT timehh:mm:ss
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
-hh:mm:ss
-
-hh:mm:ss
Default
GMT timehh:mm:ss
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
7872 ( 1EC0 hex ) -20°C
-
1280 ( 500 hex ) 80°C
Default
Not Applicable °C
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
7872 ( 1EC0 hex ) -20°C
-
1280 ( 500 hex ) 80°C
Default
Not Applicable °C
Type
Read Only
39681 ( 9B01 hex )
Displays the heatsink temperature at the end of the last successful start -1
Last temperature -1
16 bit (Highbyte=b11-b8, LowByte=b7-b0)
Ta >= 0 b12=0 Ta < 0 b12=1
bit12=0 [HighByte*16 + LowByte/16]
bit12=1 256-[HighByte*16 + LowByte/16]
39680 ( 9B00 hex )
Displays the heatsink temperature at the end of the last successful start
Last temperature
16 bit (Highbyte=b11-b8, LowByte=b7-b0)
Ta >= 0 b12=0 Ta < 0 b12=1
bit12=0 [HighByte*16 + LowByte/16]
bit12=1 256-[HighByte*16 + LowByte/16]
39131 ( 98DB hex )
Displays the event time
Last peak stop current -9 ( Time )
6 Bytes
Time(ms) since midnight (bytes5,4,3,2) and
Days since 01/01/1984 (bytes1,0)
39128 ( 98D8 hex )
Displays the event time
Last peak stop current -8 ( Time )
6 Bytes
Time(ms) since midnight (bytes5,4,3,2) and
Days since 01/01/1984 (bytes1,0)
39125 ( 98D5 hex )
Displays the event time
Last peak stop current -7 ( Time )
6 Bytes
Time(ms) since midnight (bytes5,4,3,2) and
Days since 01/01/1984 (bytes1,0)
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 39 of 59