SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0
-
1 ( 1 hex ) 1
Default
0 ( 0 hex ) 0
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0A
-
10000000 ( 989680 hex ) 10000A
Default
0 ( 0 hex ) 0A
Type
Read Only
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) 0A
-
10000000 ( 989680 hex ) 10000A
Default
0 ( 0 hex ) 0A
Type
Read Only
38402 ( 9602 hex )
Displays the peak current of the last successful start -1
Last peak start current -1
32 bit unsigned
Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
38400 ( 9600 hex )
Displays the peak current of the last successful start.
Last Peak Current
32 bit unsigned
Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
38080 ( 94C0 hex )
STATUS INDICATION : iERS Active
iERS Active
On : Indicates that the Unit is operating in the iERS energy saving Mode.
Off : The iERS saving mode has been disabled either internally or via ModbusPNU 21120
8 bit unsigned
To map to digital output refer to PNU11584-PNU11587
Binary value
37824 ( 93C0 hex )
STATUS INDICATION : Current Limit
Current Limit
On : The ramp is being held because "Current Irms" is greater or equal to " Current Limit Level "
Off : The ramp is not being held because " Current Irms " is less than " Current Limit Level "
8 bit unsigned
To map to digital output refer to PNU11584-PNU11588
Binary value
37760 ( 9380 hex )
STATUS INDICATION : End Of Start
End Of Start
On : Indicates that the Soft Start ramp has been completed.
Off : The Unit is disabled or ramping down.
8 bit unsigned
To map to digital output refer to PNU11584-PNU11587
Binary value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 31 of 59