Trip Code Descriptions
One or all of the phases are missing on the motor side during the instant of start up
401
Motor Side Phase Loss
T1 T2 or T3 phase are missing or at a very low level.
Check that the motor is connected to T1 T2 and T3. Ensure any disconnecting device between the Unit and the motor is closed at the instant of start up.
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
One or more of the internal control thyristors (SCRs) have failed to turn on properly. (Delta "Firing Mode")
350-358
Thyristor Firing Trip
The Unit has detected that the SCRs are not operating as expected.
Check all incoming and outgoing connections.
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
One or more of the internal control thyristors (SCRs) have failed to turn on properly. (In-Line "Firing Mode")
301-308
Thyristor Firing Trip
The Unit has detected that the SCRs are not operating as expected.
Check all incoming and outgoing connections.
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Thermal sensor Failure
208
Thermal Sensor Trip
The internal temperature sensor has failed
Contact the supplier
The Trip Number shown in PNU Name is a
decimal value
Trip Code Descriptions
Internal heatsink temperature has exceeded 90°C
201
Maximum Temp. Exceeded
It is possible the Unit is operating outside specified limits.
Check enclosure ventilation and airflow around the Unit. If the unit trips immediately the internal temperature sensor could be faulty.
The Trip Number shown in PNU Name is a
decimal value