SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) On
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) On
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) On
Type
Read/Write
53795 ( D223 hex )
Allows a trip to be forced using one of the digital inputs
External Trip
On : Trips when the programmed input is active
8 bit unsigned
Off : External Trip is disabled
Binary value
53794 ( D222 hex )
A single PTC motor thermistor or set of PTC motor thermistors can be connected to the PTC terminals.
PTC Motor Thermistor Trip
On :The Unit will trip if the motor thermistor exceed its response temperature or the PTC input is open circuit
8 bit unsigned
Off : The Unit will continue to operate.
Binary value
53793 ( D221 hex )
The shearpin is an electronic equivalent of a mechanical shearpin
Shearpin Trip
On : The Unit will trip. This feature is not active during soft start and soft stop.
8 bit unsigned
Off: The Unit will continue to operate regardless of motor current level
Binary value
53792 ( D220 hex )
The Unit has an "Overload" function that is an electronic equivalent to a thermal overload.
Overload Trip
On : The Unit will trip when the "Overload" capacity (ModbusPNU 33408) exceeds 100%
8 bit unsigned
Off: The Unit will continue to operate regardless of motor current level
Binary value
53791 ( D21F hex )
Selects trip or continue if the stop current limit has been active for too long
Stop Current Limit Trip
On : The Unit will trip
8 bit unsigned
Off: The stop will continue regardless of the motor current level
Binary value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016
Page 46 of 59