SWI-SGY-USB-V05700
Description
Text in quotes refer to a Synergy parameter or function, for example "Start Time"
i-synergy = synergy Class 10 current, i-rated = synergy Class20 / Class30 current, i-motor = motor current
[ SGY1051400 SGY2070000 SGY3023400 ]
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) On
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) Off
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
1 ( 1 hex ) On
Type
Read/Write
PNU Number
PNU Name
PNU Format
PNU Note
Range
0 ( 0 hex ) Off
-
1 ( 1 hex ) On
Default
0 ( 0 hex ) Off
Type
Read/Write
53803 ( D22B hex )
For safety purposes the Unit has been designed to trip if the front cover is open
Cover Open Trip
On : The Unit will trip if the front cover is open. This trip is active at all times.
8 bit unsigned
Off : The Unit will continue to operate with the cover open
Binary value
53800 ( D228 hex )
Detects if the Control Board has failed to operate normally
Operation 3 Trip
On : Operation 3 trip enabled.
8 bit unsigned
Off : Operation 3 trip disabled.
Binary value
53799 ( D227 hex )
Detects if the logging function has failed to operate normally
Operation 2 Trip
On : Operation 2 trip enabled.
8 bit unsigned
Off : Operation 2 trip disabled.
Binary value
53798 ( D226 hex )
Detects if the keypad Board has failed to operate normally
Operation 1 Trip
On : Operation 1 trip enabled.
8 bit unsigned
Off : Operation 1 trip disabled.
Binary value
53796 ( D224 hex )
Detects if the communications bus has failed or become inactive. To keep the bus active there must be at least one Modbus read or write (any PNU)
during the "Timeout ms" period (ModbusPNU 15808)
Communications Trip
On :Communication trip enabled.
8 bit unsigned
Off : Communication trip disabled.
Binary value
MAN-SGY-012-V11 EC 5195
Fairford Electronics Ltd - Synergy Modbus RTU Programming Manual - 22nd February 2016