Power line connection
6.
Ref.1912
· 237 ·
DDS
HARDWARE
IT diagram
Distribution diagram that has no direct connection to ground and the
conductive parts of the installation are connected to ground.
With IT type distribution diagrams, the differential breaker is used assuming
that the capacitance of mains with respect to ground is large enough to
ensure that a minimum fault current flows with the same magnitude as that
of the operating differential current assigned. Otherwise, its use is not
necessary.
for properly installing the DDS system with an IT type
distribution diagram.
F. H6/6
IT type distribution diagram.
DDS
L1
L2
L3
SECONDARY
WINDING OF THE
LINE TRANSFORMER
OF THE PLANT
DIFFERENTIAL
BREAKER
MAINS
FILTER
L1
L2
L3
DDS
DIFFERENTIAL
BREAKER
SECONDARY
WINDING OF THE
LINE TRANSFORMER
OF THE PLANT
MAINS
FILTER
IT diagram
MANDATORY.
With an IT distribution diagram, always install the DDS
system to mains through an isolating transformer.
INFORMATION.
Note that with an IT type distribution diagram, mains can also
be controlled through an isolation watching device. Both protection
measurements are compatible with each other.
i
Summary of Contents for DDS APS-24
Page 1: ...DRIVE DDS Hardware manual Ref 1912...
Page 6: ...6 Ref 1912 DDS HARDWARE 6 I This page intentionally left blank...
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 16: ...Ref 1912 DDS HARDWARE 16...
Page 20: ...Ref 1912 DDS HARDWARE 20...
Page 179: ...3 Drives Ref 1912 179 DDS HARDWARE...
Page 180: ...3 Drives Ref 1912 DDS HARDWARE 180...
Page 200: ...4 AUXILIARY MODULES Auxiliary modules Ref 1912 DDS HARDWARE 200...
Page 260: ...7 Cables Ref 1912 DDS HARDWARE 260...
Page 397: ...Sales models 12 Ref 1912 397 DDS HARDWARE 12 9 Order example F H12 21 Order example...
Page 404: ...13 Compatibility Ref 1912 DDS HARDWARE 404...
Page 405: ......