EZ-TEXT-M-E

Text Panel Hardware Manual

EZSeries Set Point Display  Text Panels are supplied with two  ferrite cores that 
should be attached to the cables prior to installation of the EZSeries Set Point 
Display  Text Panel.  These cores are 

required to suppress  EMI emissions

 that 

are conducted through the Power Cable and the Communications Cable.  The 
fi gure, below, shows the ferrite cores properly installed.  Attach the cores within 
one inch of the EZSeries Set Point Display  Text Panel connector.  The cable 
should be snugly wrapped  once around the core, providing two passes through 
the core.  

The 

 Power Cable

 

Core 

is a solid ferrite cylinder.  The Power Cable should pass 

once through the core, be looped around and pass through a second time.  Pull 
the excess cable so that it rests snugly against the outside of the core.  

The

  Communications Cable Core 

is a snap-together, split, ferrite core.  This 

core can be installed on a fi nished cable. Lift the latch to open the core.  Wrap 
the wire through the core center, snugly around the outside, and again through 
the center.  Close the core until the latch snaps. Ensure that the cable jacket is 
not pinched between the two halves of the core.  The fi nished cable should look 
similar to the drawing shown below.

 EMI Noise Filter Installation

Summary of Contents for EZ-220

Page 1: ...ent 9 Front Panel Features 10 Operator Controls and Indicators 10 Annunciator Lamps 11 Data Entry Keypad Pushbuttons 11 PLC Message LED 11 Control Pushbuttons 12 Function Pushbuttons 12 Pushbutton LED...

Page 2: ...ssage Types 36 Displaying PLC Messages 36 PLC Message LED 35 Arrow Adjustment Entry 38 Numeric Keypad Entry 38 Annunciator Lamps 38 PLC Message LED 38 Displaying Local Messages 39 Local Message File S...

Page 3: ...Still Need Help 91 Warranty Repairs 92 Out of Warranty Repairs 92 Frequently Asked Questions FAQs 93 Appendix A A 1 EZSeries Text Panel Application Worksheet A 2 Appendix B B 1 Allen Bradley B 2 Direc...

Page 4: ...red if this equipment is not used in accordance with this manual Only replacement parts supplied by EZAutomation or its agents should be used Technical Support If you need assistance please call our t...

Page 5: ...he EZSeries Set Point Display Set Point Display Panel What you need to get started Need HELP Models PLCs Supported by EZSeries Set Point Display Set Point Display Panel Accessories and Optional Equipm...

Page 6: ...features of all EZSeries Set Point Display Set Point Display Panels Lists the PLCs supported by the panels by brand model and protocol Lists the part numbers for PLC cables and the programming cable...

Page 7: ...luding Fuse Reset Precautions Chemical Compat ibility Cleaning and Gasket Replacement Troubleshooting section aids in diagnosing problems you might encounter when installing or operating the panel Pro...

Page 8: ...hbuttons that allow you to trigger PLC actions with the push of a button These pushbuttons are used for input signals to the PLC Each pushbutton can be configured to function as one of three switch ty...

Page 9: ...f the most important features of the EZSeries Set Point Display Set Point Display Programming Software is the availability of context sensitive onscreen help To access the Help windows simply press th...

Page 10: ...data variables per message built in menu system EMI filtered power supply to reduce communication problems to EZSeries Set Point Display Set Point Display Te Panel wiring diagrams Technical Support A...

Page 11: ...ter height of 0 22 5 55 mm External dimensions are 5 x 7 4 x 1 6 EZ 220 Above with Vacuum with LCD Display EZ 220L 2 lines by 20 characters LCD display Character height 0 316 8 06 mm External dimensio...

Page 12: ...U 311 xx 411 xx 512 aa 612 xx Modbus RTU Omron C200 C500 CQM1 CPM1 Host Link Direct Logic DL05 DL06 K Sequence DirectNet Modbus Koyo addressing DL105 K Sequence DL205 D2 230 K Sequence D2 240 K Sequen...

Page 13: ...1 port DL340 RS 232C EZP 4CBL 1 Direct Logic PLC 15 pin Dsub port DL405 RS 232C EZP 4CBL 2 Direct Logic PLC 25 pin Dsub port DL405 DL350 DL305 DCU and all DCM s RS 232C EZP 90 30 CBL GE 90 30 and 90 7...

Page 14: ...he panel indicators and controls please refer to Chapter 4 Tutorial Operator Controls and Indicators Each EZSeries Set Point Display Set Point Display Panel provides sealed membrane Pushbuttons for op...

Page 15: ...eric keypad Use this keypad to enter or change embedded data values To update or enter a data value the enter button must be pressed to select the data value Then you may use the numeric keypad or the...

Page 16: ...d as one of three switch types Alternate Momentary or Panel Set PLC Release described on page 69 They are configured as discrete input signals to the PLC These pushbuttons are labeled F1 through F5 or...

Page 17: ...n or instructions to the operator and are displayed in a menu hierarchy They can also be programmed to display values from a PLC register that the operator may change using the EZSeries Set Point Disp...

Page 18: ...push buttons Five user defined pushbuttons and four control push buttons Numeric keypad five user defined pushbuttons and four control push buttons Service Power 24 VDC 20 30VDC operating range Power...

Page 19: ...Hardware Installation In this chapter Custom Labels EMI Noise Filter Installation Mounting DIN Clip Mounting Connections and Wiring 2...

Page 20: ...you installed your programming software You must have Word installed on your computer to open this document This document will help you create your labels Two sheets of cover stock have also been shi...

Page 21: ...abel into the slot Hold the overlay up with the ramp tool and start the custom label into the slot illustration 4 5 Once the label has been placed into the slot move the ramp tool behind the label ins...

Page 22: ...around the core providing two passes through the core The Power Cable Core is a solid ferrite cylinder The Power Cable should pass once through the core be looped around and pass through a second tim...

Page 23: ...panel comes with all the necessary mounting hardware required for stud mounting DIN Clips P N EZP BRK 2 must be ordered separately Models EZ 220 200V 420 Outline Dimensions and Mounting Template STUD...

Page 24: ...t Panel Hardware Manual Model EZ 220P EZ 220PV Outline Dimensions Mounting Studs 4 total STUD Mounting Use the 4 studs and 4 nuts with captive washers to secure the unit to the mount ing surface Requi...

Page 25: ...Manual Mounting Studs 4 total Model EZ 220L Outline Dimensions and Mounting Template STUD Mounting Use the 4 studs and 4 nuts with captive washers to se cure the unit to the mount ing surface Require...

Page 26: ...screw They provide an alternative to bolting the panel into the mounting surface There are 4 square holes in the chassis two on the top and two on the bottom Insert the clip flange into this hole and...

Page 27: ...23 EZ TEXT M E Text Panel Hardware Manual Connections and Wiring EZSeries Text Panel Application...

Page 28: ...s These LEDs illuminate to show whether the unit is sending or receiving data See page 91 Serial Port This port may be used to connect the programming computer or a PLC see page 27 Use programming cab...

Page 29: ...hese LEDs illuminate to show whether the unit is sending or receiving data See page 91 Serial Port This port may be used to connect the programming computer or a PLC see page 27 Use programming cable...

Page 30: ...LEDs illuminate to show whether the unit is sending or receiving data See page 91 Serial Port This port may be used to connect the programming com puter or a PLC see page 27 Use programming cable P N...

Page 31: ...ou power up the EZSeries Set Point Display Text Panel it will come up in RUN Mode While in RUN Mode the Serial Port will only communicate with a PLC To program the panel and have the Serial Port commu...

Page 32: ...28 EZ TEXT M E Text Panel Hardware Manual Connect a PLC Connect your PLC to the EZSeries Set Point Display Text Panel with one of the cables listed below P N EZTEXT PGMCBL EZSeries Text Panel...

Page 33: ...s Memory Mapping PLC Data Registers Pushbuttons LEDs PLC Message Embedded Data PLC and Local Messages Message Types Displaying PLC Messages PLC Messages LED Displaying Local Messages Local Message Fil...

Page 34: ...rectLogic examples and other PLC solutions such as Allen Bradley please refer to the PLC manufacturer s manual Memory Mapping PLC Data Registers Pushbuttons Register LEDs Register Annunciator Lamps Re...

Page 35: ...ton on the panel Bits 10 14 are set when the Panel Set and PLC Release Option is selected for the corresponding Function Pushbutton and the Release Bit for that button is set by the PLC in the LED BIT...

Page 36: ...nowledging to the PLC that it has reset the button 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 NA NA NA NA NA NA NA NA NA NA LAMP 3 LAMP 3 LAMP 2 LAMP 2 LAMP 1 LAMP 1 Annunciator Lamps Annunciator Lamps use...

Page 37: ...message number and displays the message associated with the value i e a value of 3 displays message 3 Embedded Data Registers Each message can have up to three embedded data values DATA 1 DATA 2 and D...

Page 38: ...PLC controlled decimal point DATA 2 16 Bit Register READ ONLY This is a PLC register that contains the second of three possible embedded data values on a line for the message displayed You may manual...

Page 39: ...ressing Ctrl 2 or F6 and are represented by a 2 for each numeric digit displayed in blue DATA 3 values are entered into the message by pressing Ctrl 3 or F7 and are represented by a 3 for each numeric...

Page 40: ...ed by the PLC or manually inserted DATA 2 and DATA 3 allow you to manually insert a decimal point The maximum number of data values per message is three Data type and decimal points are programmed whe...

Page 41: ...the interactive message is displayed the operator can enter data Check the PLC product user manual to verify which data formats are supported Depending on the PLC the data format will be either Binar...

Page 42: ...hbutton and the value will be placed in the data register for display and the bit is set Numeric Keypad Entry Numeric Keypad entry is used when a decimal point is being used and is the preferred metho...

Page 43: ...ers The EZSeries Set Point Display Text Panel Programming Software only allows 19 characters for folder text when you are configuring the Local Messages You may use the UP DOWN Arrow buttons to scroll...

Page 44: ...owed multiple Messages and subfolders Basic Structure You cannot change this It is the Root Level All messages and folders stem from here This is not displayed on the panel In this example of the Loca...

Page 45: ...is contains 3 messages and one subfolder also with 3 messages Message 14 Folder A message Viewing the menu from open Folder B Folder B Folder is open and it contains 3 messages and one subfolder with...

Page 46: ...42 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...

Page 47: ...Set Point Display Text Panel Setup Installing EZSeries Set Point Display Text Panel Pro gramming Software Installation Screens Tutorial Plan the Project using Application Worksheets Create a Project w...

Page 48: ...WN arrows to increase or decrease the contrast Internal Software and Hardware Revisions While in SETUP Mode the Panel Hardware Revision Driver Revision Boot Revision and Exec Firmware Revision numbers...

Page 49: ...rt number EZ TEXTEDIT E The software is used to download your configuration before connecting the panel and communicating with a PLC Help Topics are provided to help you configure your panel You desig...

Page 50: ...nt Display Text Panel If you wish to select another destination click on the Browse button To complete the installation click on Next button That s all there is to it The EZSeries Set Point Display Te...

Page 51: ...EZSeries Set Point Display Text Panel Programming Software Let s start by filling out the application worksheet found in Appendix A For tutorial purposes we have already filled in the information For...

Page 52: ...hapter 3 Learning the Features Shown here are the bit addresses for the Button PLC Word V40600 and LED PLC Word V40601 in this tutorial Please note that any unused bit address SHOULD NOT BE USED in yo...

Page 53: ...oject planning we ll create four Local Messages using the Local Message Worksheet These messages will be configured later in our EZSeries Set Point Display Text Panel Demo Project using the EZSeries S...

Page 54: ...ur project planning is creating three PLC Messages using the PLC Message Worksheet These messages will be configured later in our EZSeries Set Point Display Text Panel Demo Project using the EZSeries...

Page 55: ...cable Apply 24 VDC to the panel power connector 1 From the Welcome screen click on the New System button 2 The Create Project window will appear Type in EZSeries Set Point Display Text Panel Demo Proj...

Page 56: ...Under Panel Type click on the panel type you are using to highlight it A picture of the panel will appear under Panel Preview and key features of the panel are displayed under Panel Attributes c Clic...

Page 57: ...have selected In this case DirectLogic K Sequence Set the attributes to match those in the screen capture below Click on the OK button 5 In Step 3 you will configure the Buttons LEDs Messages and Pane...

Page 58: ...hoices Select Alternate for F1 and F5 Momentary for F2 and F3 and Panel Set PLC Release for F4 c Assign a PLC Word for the LEDs and the Buttons These PLC Words should be a BIT Register d Click on OK t...

Page 59: ...ick on the Press to accept Message edit button Step 3 b Click on the Process Control Folder to select it and then click on the Add Local Message button c Enter Press F1 to Start Y0 in the Message Text...

Page 60: ...message DATA 1 h Click on the Process Control Folder then click on Add Local Message i In the Message Text field type in Load Part leave a space and then press F5 or Ctrl 1 four times DATA 1 will appe...

Page 61: ...ype in the Message Text field PLC Release Bit Ackn f Click on the Press to accept Message edit button to save it g Click on the Add next PLC Message button h Type in the Message Text field ESC for Loc...

Page 62: ...in V3001 in the Line Two field Select BCD as the DATA Type b The panel beeper is defaulted to Yes If you do not want to hear the beeper each time a button is pressed select No under Enable Beeper c Cl...

Page 63: ...ress the UP and DOWN arrows on the EZSeries Set Point Display Text Panel simultaneously The panel display will read SETUP MODE on the first line 16 Click on the Start button on the Writing to Panel sc...

Page 64: ...using a DirectLogic DL05 PLC To configure the PLC we are using DirectSOFT Programming Software The purpose of this part of the tutorial is to show you how to configure your PLC to communicate with an...

Page 65: ...61 EZ TEXT M E Text Panel Hardware Manual...

Page 66: ...e displayed on the first line 2 Press the enter button to open the folder Level 2 Local Message Press F1 to Start Y0 will be displayed Use the arrow buttons to scroll through the messages Press the es...

Page 67: ...Configure New System Step 1 Select Panel Step 2 Select PLC Step 3 Panel System PLC Address Setup Configure Local and PLC Messages Configure Existing System Connect to Panel View Panel Status and Firmw...

Page 68: ...ew System This section will take you through the steps necessary to configure a new system edit an existing system view panel status and upgrade the EZSeries Set Point Display Text Panel firmware We r...

Page 69: ...onfigure the EZSeries Set Point Display Text Panel program The following screen will appear 3 Enter a name for the project in the File name field Navigate to the directory and folder where you want to...

Page 70: ...w next to the Select PLC field Choose the PLC and Protocol type you are using 6 Click on Press for Communication Configuration for Selected PLC button A PLC Attributes dialog box specific to your type...

Page 71: ...ations parameters match the PLC port settings There will be a selection for PLC timeout When the panel sends a message to the PLC and does not receive a response or does not understand the response it...

Page 72: ...word Protection is only available in models EZ 220P 220PV 11 First select the LED Control for the first button LED Bit 0 You may choose to have the LED controlled By Button By Button Flash or By PLC M...

Page 73: ...3 Click on OK to save your Button LED control selections 14 Now you are ready to configure Local and PLC Messages Click on the Message button as shown to the right The following screen will appear 19...

Page 74: ...DATA 2 or F7 or CTRL 3 for DATA 3 Each press of the function key will enter one data value digit You may enter up to 5 characters depending on the data type In the message the data will be represente...

Page 75: ...three annunciator lamps White represents OFF 17 Click on the OK button to save the register address and exit the screen 18 Now you are ready to configure Local and PLC Messages Click on the Message b...

Page 76: ...nfigured in your PLC ladder logic program Place a check mark in the box next to PLC Controlled Decimal Point and then enter the PLC Address where the control resides This is DATA 1 only you cannot con...

Page 77: ...r on the first line of the EZSeries Set Point Display Text Panel display when it is in Run Mode Second programmed message displays on second line etc up to four lines depending on the type of panel yo...

Page 78: ...Number of Messages of 256 programmed are also displayed for your information b If you want to embed data values from a PLC register in the message press F5 or Ctrl 1 for DATA 1 F6 or Ctrl 2 for DATA...

Page 79: ...re than one message number e g you have programmed messages 1 through 4 skipped messages 5 and 6 and then programmed 7 and highlight message 7 and click on Insert a PLC message the following dialog bo...

Page 80: ...76 EZ TEXT M E Text Panel Hardware Manual...

Page 81: ...77 EZ TEXT M E Text Panel Hardware Manual...

Page 82: ...out are not available for the EZSeries Set Point Display Text Panel model you have selected The PLC controller you have selected and the Project Name are also displayed along with the Total Number of...

Page 83: ...the EZSeries Set Point Display Text Panel Icon to open the EZSeries Set Point Display Text Panel Programming Software The following screen will appear 2 Click on the Existing System button to edit an...

Page 84: ...nel Status Firmware Version button to view the panel status The Panel Status window will open An example is shown below Picture of the panel type you are connected to Key features of the current panel...

Page 85: ...e 1 Place the panel in Setup Mode by pressing the UP DOWN arrows on the EZSeries Set Point Display Text Panel simultaneously 2 Under the Panel Menu click on Upgrade Firmware The following screen will...

Page 86: ...nd the upgrade to the panel 4 Select the appropriate COM port under Port Selected if necessary and click on the Start button to begin downloading the firmware to the EZSeries Set Point Display Text Pa...

Page 87: ...2 Click on the Cancel button on the Downloading Firmware window Upgrade Firmware when you press the Start button the panel will display SELF TESTING while the upgrade is initializing When the downloa...

Page 88: ...84 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...

Page 89: ...aintenance Fuse Reset Precautions Screen Overlay Chemical Compatibility Screen Overlay Cleaning Gasket Replacement Troubleshooting Panel Configuration Problems PLC Errors Warranty Repairs Out of Warra...

Page 90: ...is provided to make you aware of the general compatibility between chemicals that may be present in your work environment and the polyester surface of the overlay Use the chart to determine those che...

Page 91: ...thylene N Phenol Crystals N Phosphoric Acid 5 E Phosphoric Acid 85 G Pine Oil E n Butyl Acetate N n Butyl Alcohol F sec Butyl Alcohol F tert Butyl Alcohol F Butyric Acid N Calcium Hydroxide N Calcium...

Page 92: ...asket adhesive side down over the panel gasket surface and press firmly In this section we will explain how to isolate potential problems If you cannot Potassium Hydroxide 1 N Potassium Hydroxide conc...

Page 93: ...of the unit observe Serial Port Communication TXD RXD LEDs while attempting to Upload Download a program Both LEDs should be slowly and alternately flashing to indicate that the programming PC and the...

Page 94: ...e Appendix C of this manual or the EZSeries Set Point Display Text Panel Programming Software Help for error messages for your type PLC Each PLC Help topic lists the error messages and provides an exp...

Page 95: ...ion for the PLC type protocol baud rate parity stop bits and address number Use the PLC manual to determine the proper settings 3 If you have configured your own cable verify cable pinout using the PL...

Page 96: ...an answer to give us a call from 6 a m to Midnight CST at the number above and we will be glad to assist you Warranty Repairs If your EZSeries Set Point Display Text Panel is under warranty contact EZ...

Page 97: ...plexer and one multiplexer per serial port The second method is to connect one panel per serial port 4 What is the maximum number of messages I can have in a project The maximum amount of PLC and Loca...

Page 98: ...the PLC Message Line Addresses up to four if using the EZ 420 When the message number is placed in this register the panel will display the message corresponding with that number Example I want to di...

Page 99: ...count towards the maximum number of allowed messages in a project 256 17 Can you copy and paste messages Yes you can copy and paste messages Currently however you can copy or paste only one message a...

Page 100: ...96 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...

Page 101: ...Appendix A In this appendix EZSeries Set Point Display Text Panel Application Worksheets Local Message Worksheet PLC Message Worksheet A...

Page 102: ..._____________________ Panel Acknowledge of PLC Release PLC Address ACK F1 _______________ ACK F2 _______________ ACK F3 _______________ ACK F4 _______________ ACK F5 _______________ __________________...

Page 103: ...cimal ________ ___________________ DATA 2 ________ DATA 3 BCD Binary BCD Binary BCD Binary Read Write Min Max Folder 19 characters Message 20 characters Folder Message Level 1 2 3 4 DATA 1 ___________...

Page 104: ...cimal ________ ___________________ DATA 2 ________ DATA 3 BCD Binary BCD Binary BCD Binary Read Write Min Max Folder 19 characters Message 20 characters Folder Message Level 1 2 3 4 DATA 1 ___________...

Page 105: ...___________ Read Only DATA 2 ________ DATA 3 BCD Binary BCD Binary PLC Decimal ________ ___________________ BCD Binary Read Write Min Max 20 characters Message No _________ DATA 1 ____________________...

Page 106: ...___________ Read Only DATA 2 ________ DATA 3 BCD Binary BCD Binary PLC Decimal ________ ___________________ BCD Binary Read Write Min Max 20 characters Message No _________ DATA 1 ____________________...

Page 107: ...rams for the following PLCs Allen Bradley Aromat Control Techniques Control Technology Corporation CTC DeviceNet Ethernet General Electric Idec Mitsubishi Modicon Omron Profibus Direct Logic Siemens S...

Page 108: ...nt Display Text Panel to PLC Cables If EZAutomation provides the cable the part number is included with the description Wiring diagrams for some PLCs are provided so that you may construct Allen Bradl...

Page 109: ...B 3 Text Panel Hardware Manual Allen Bradley Micrologix 1000 1200 1500 RS 232 P N EZP MLOGIX CBL DirectLogic PLC RJ 12 D05 DL105 DL205 DL350 and DL450 RS 232 P N EZP 2CBL...

Page 110: ...B 4 Text Panel Hardware Manual DirectLogic PLC 15 pin D SUB DL405 RS 232 P N EZP 4CBL 1 DirectLogic PLC VGA 15 pin 250 RS 232 P N EZP 2CBL 1...

Page 111: ...B 5 Text Panel Hardware Manual DirectLogic PLC RJ 11 340 RS 232 P N EZP 3CBL DirectLogic PLC 25 pin D SUB DL405 350 305 DCU and all DCMs RS 232 P N EZP 4CBL 2...

Page 112: ...B 6 Text Panel Hardware Manual General Electric 90 30 and 90 70 15 pin D SUB RS 422 P N EZP 90 30 CBL Mitsubishi FX Series 25 pin RS 422 P N EZP MITSU CBL...

Page 113: ...B 7 Text Panel Hardware Manual Modicon ModBus 9 Pin D SUB RS 232 P N EZP MODRTU CBL Mitsubishi FX Series 8 pin MINI DIN RS 422 P N EZP MITSU CBL 1...

Page 114: ...B 8 Text Panel Hardware Manual Omron C200 C500 RS 232 P N EZP OMRON CBL Siemens S7 MPI Adaptor P N EZP S7MPI CBL...

Page 115: ...B 9 Text Panel Hardware Manual Control Techniques Unidrive 4 wire RS 422 D Sub Female 9 position P N EZP CTRLUNI CBL The hardware connection for the Control Techniques Unidrive PLCs is RS 422 4 wire...

Page 116: ...e Manual Control Technology Corporation CTC PLC RS232 RJ 12 Port P N EZP CTCBI CBL The hardware connection for the CTC2600 and CTC2700 is RS 232C Texas Instruments 505 Series PLC RS 232C D Sub Female...

Page 117: ...B 11 Text Panel Hardware Manual Texas Instruments 545 1102 Series PLC RS 422A D Sub Male 9 pin P N EZP TX545 CBL Texas Instruments 545 1104 Series PLC RS 422A D Sub Female 9 pin P N EZP TX545 CBL1...

Page 118: ...B 12 Text Panel Hardware Manual Idec MicroSMART PLC RS232 8 pin Mini DIN Male P N EZP IDECS CBL...

Page 119: ...B 13 Text Panel Hardware Manual Aromat PLC RS232 Mini DIN 5 pin Male Connector P N EZP ARCOL CBL EZAutomation EZPLC 9 Pin D SUB RS 232 P N EZP CBL...

Page 120: ...B 14 Text Panel Hardware Manual This page intentionally left blank...

Page 121: ...Appendix C In this appendix PLC Driver Error Messages EZSeries Set Point Display Text Panel Error Messag es EZSeries Set Point Display Text PanelProgramming Software Error Messages C...

Page 122: ...s an invalid set of attributes The default attributes will be used when this occurs 0x0020 PLC bad checksum CMD X This occurs when a reply with an invalid checksum is received by the unit The command...

Page 123: ...curs when there are too many registers on the display to be monitored The number of registers on the display must be reduced 0x0008 PLC MSG Time out CMD X This occurs when the unit does not receive a...

Page 124: ...ex Protocol 0x0000 No error 0x0001 Incompatible Revision This error will be displayed when the driver and exec have incompatible revision 0x0002 PLC error incorrect map size This error occurs when an...

Page 125: ...0x0400 PLC error no reply This occurs when the DF1 modules indicate the PLC has no reply to the last message It is usually displayed when the unit reestablishes communications after a PLC message tim...

Page 126: ...250 DCM D3 350 D3 350 DCM D4 430 D4 440 D4 450 DL405 Series all with DCM 0x0000 No Error 0x0001 Incompatible Revision This error will be displayed when the driver and exec have an incompatible revisi...

Page 127: ...Reply The driver received an incorrect or unexpected reply from the PLC with address nnn 0x0020 Error PLC nnn error The driver received a ModBus message exception code from the PLC The error strings...

Page 128: ...using defaults The driver received attributes it could not use The default values for all PLC attributes will be used DirectNet Protocol DL330 DL340 Direct Logic PLC Models D3 330 330P D3 340 0x0000...

Page 129: ...ing the space after the equal sign will be the last character in the error string 0x0008 Invalid PLC Attributes using default The attributes passed from the program loader or the existing attributes i...

Page 130: ...eouts The timeout time specifies the amount of time the panel will wait for a reply to a message before triggering an error Each message sent to the PLC must be acknowledged by the PLC The acknowledgm...

Page 131: ...was attempted 0x0080 PLC time out PLC nnn The EZSeries Set Point Display Text Panel is unable to communicate with the PLC with address nnn This may be corrected by increasing the time out time or incr...

Page 132: ...lid Write to EZSeries Set Point Display Text Panel register r This error occurs when an attempt is made to write to a register r when r is mapped to read only element 0x0400 PLC Message Time out This...

Page 133: ...his error occurs 0x0080 Invalid Write to Panel register nnnn A write was attempted to an internal Panel register number nnnn that has been mapped as a read only location 0x0100 PLC Communication Timeo...

Page 134: ...d to edit to a read only data item INVALID This message indicates that the operator has entered an illegal password NO DATA SET This message indicates that the operator has tried to enter a data item...

Page 135: ...all other applications and retry 2 reboot the system 3 reinstall the software Error P006 PLC1 is not compatible with PLC2 Do you want to change the PLC anyway Error P007 Unable to rebuild the address...

Page 136: ...mum replay length 70 Solution If you receive this error message consistently please report it to technical support Standard reply error messages PLC Address Error Messages Error T001 PLC Address count...

Page 137: ...ect map file Error T006 Error in reading PLC Addresses Reason Unable to generate PLC address while reading from the panel Solution Project in the Panel is corrupted Reload the project to the panel Err...

Page 138: ...nvalid PLC driver file Solution If you receive this error message consistently please report this to technical support Error Z005 The Maximum message length has exceeded Reason Maximum message length...

Page 139: ...d string was not sent from the Panel to the PLC correctly or the checksum in the message was incorrect Error 5 FMT_ERR Screen Message FORMAT ERROR Condition Command string was missing characters or so...

Page 140: ...VALID CHECKSUM SENT Txxxxx xxx BB Condition This error will be displayed if the driver sent the PLC a message with a bad checksum Error 4 ILLEGAL_REG_READ Screen Message INVALID REGISTER READ Txxxxx x...

Page 141: ...ATE Screen Message INVALID DRIVER STATE Condition Never should occur Error 15 GENERAL_ERROR Screen Message ERROR CODE xxx Condition Never should occur Error 16 LAST_ERROR Screen Message N A Condition...

Page 142: ...e too many registers on the display to monitor 0x0004 Invalid checksum received An invalid checksum was received in a message from the PLC 0x0008 PLC Error Check PLC Status The PLC has sent an error c...

Page 143: ...73 Binary 36 73 Binary Coded Decimal 37 binary data format 37 Bit 69 bit addresses 48 blank messages 77 Boot Revision 44 Button Action 69 Buttons Bit Write PLC Word 70 BUTTONS BIT WRITE PLC WORD FROM...

Page 144: ...LC Messages 36 DOWN arrow 12 download 45 Driver Errors ALLEN BRADLEY PLCs C 2 Micrologix SLC 500 DF1 Full Duplex C 4 Micrologix SLC 500 DH 485 AIC C 2 PLC5 with DF1 Protocol C 3 DirectLogic PLCs C 5 D...

Page 145: ...28 EZTEXT2xy 82 EZTEXT4xy 82 EZTEXTSPxy 82 EZTOUCH6 GSK 88 EZTOUCH8 GSK 88 F F1 function key 5 F5 35 73 F6 35 73 F7 35 73 factory repairs 92 features 4 6 30 ferrite cores 18 File name 65 Firmware 81 f...

Page 146: ...N EZ B 7 Mitsubishi FX Series PLC Wiring Diagram B 6 B 7 25 pin RS 422A B 12 Model EZ 220 and EZ 420 EZSeries Set Point Dis play Text Panel Outline Dimension 19 Model EZ 220L Outline Dimensions and Mo...

Page 147: ...S A 5 A 6 PLC Messages 70 72 93 Line Address Setup 68 not clearing 94 PLC Registers 72 Embedded Data 33 LEDs 31 Message Registers 33 Pushbuttons 31 PLC to EZSeries Set Point Display Text Panel Inter f...

Page 148: ...age Operation 37 Static Messages 36 static text 4 13 status bit 38 Step 1 66 72 Project Information 52 Step 2 66 72 Step 3 68 subfolder 39 supply operating voltage 27 switch types 4 12 T Technical Sup...

Page 149: ...I 7 EZ TEXT M Text Panel Hardware Manual user defined pushbuttons 12 V value 73 values 35 variable point 37 VGA display 5 W Warranty Repairs 92 website 6 91 Windows 98 5 wiring diagram 27...

Page 150: ...I 8 EZ TEXT M Text Panel Hardware Manual This page intentionally left blank...

Reviews: