32
EZ-TEXT-M-E
Text Panel Hardware Manual
Example when using Panel Set & PLC Release Option for a Function
Pushbutton:
Operator Presses Button:
F1 is set by the Panel (Bit 0 in Button Word).
This is a maintained pushbutton to the PLC.
PLC Releases Button:
REL F1 is set by the PLC (Bit 10 in LED Word).
The PLC resets the panel button by setting this
bit in the ladder program.
Panel Acknowledge Button Release:
ACK F1 is set by the Panel (Bit 10 in Button Word).
This is the panel acknowledging to the PLC that
it has reset the button.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
LAMP
3
LAMP
3
LAMP
2
LAMP
2
LAMP
1
LAMP
1
Annunciator Lamps
Annunciator Lamps use one 16-bit register. All bit designations are in octal (0–7
and 10–17), used by DirectLogic PLCs. Use bits 0 through 15 for PLCs using
decimal numbering.
ANNUNCIATOR (BIT READ) PLC WORD — (TO PANEL)
LAMP 1
= Left Lamp, Bits 0 and 1
LAMP 2
= Center Lamp, Bits 2 and 3
LAMP 3
= Right Lamp, Bits 4 and 5
NA
= not used (DO NOT use for other PLC program addresses)
To have the lamps illuminate in a particular color, or not to illuminate at all, set
the bits in your PLC Ladder Logic as follows:
(BITS)
Summary of Contents for EZ-220
Page 46: ...42 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Page 65: ...61 EZ TEXT M E Text Panel Hardware Manual...
Page 80: ...76 EZ TEXT M E Text Panel Hardware Manual...
Page 81: ...77 EZ TEXT M E Text Panel Hardware Manual...
Page 88: ...84 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Page 100: ...96 EZ TEXT M E Text Panel Hardware Manual This page intentionally left blank...
Page 120: ...B 14 Text Panel Hardware Manual This page intentionally left blank...
Page 150: ...I 8 EZ TEXT M Text Panel Hardware Manual This page intentionally left blank...