Chapter 5 Fault Countermeasures and
Abnormality Handling
5.1 Fault Phenomena and Countermeasures
When the drive is abnormal, LED digit tube will display corresponding fault
codes and its contents, the drive will stop outputting, when a fault occurs, if the
motor is rotating, it will park freely, till it stops rotating. Fault types of the drive
which may occur are shown in Table 5-1, when the drive is fault, users should
carry out examination according to this table first, and record fault phenomena in
details, when technical services are required, please contact the After sale Dept. of
our company directly, or contact dealers of the company.
Table 5-1 Fault Alarming Contents and Countermeasures
Fault
Code Fault Type
Possible Fault Reasons
Countermeasures
E001
Over
current
during
acceleratio
n operation
Accelerating time is too short
Lengthen accelerating time
V/F curve is not suitable
Adjust V/F curve settings,
adjust manual torque lifting,
or
correctly
set
motor
parameters to guarantee
normal torque lifting
When instant stop occurs, restart
is implemented for rotating
motors.
The start method F2.00 is set
to rotational speed tracking
restart function
Power grid voltage is too low
Check input power supply
Drive power is too low
Select the drive of large
power level.
E002
Over
current
during
deceleratin
g operation
Decelerating time is too short
Lengthen the decelerating
time
There’s any potential energy
load or load inertia torque is
large.
External proper energy
consumption braking parts.
Drive power is low
Select the drive of large
power level.
E003
Over
current
during
constant
speed
Load changes in a sudden
Reduce sudden change in
load
Accelerating and decelerating
time is set too short
Properly
lengthen
the
accelerating and decelerating
time