9: Drive running at zero speed
When the drive output frequency is 0, but under the running status, it will output an
indication signal.
10: Simple PLC phase running completion indication
After the simple PLC current stage operation is completed, an indication signal
is
output (single pulse and the delay is less than
500ms).
11: PLC cycle completion indication
After the simple PLC completes one operation cycle, an indication signal
is output
(single pulse signal and the delay is less than
500ms).
12: Set count value arrival
13: Specified count value arrival
For 12~13, refer to F6.21~F6.22 function description.
14: Set length arrival indication
When the actual length FC.15≥FC.14 set length, an indication signal is output. The
length count terminal is the one set to function 44 in DI1~DI10.
15: Drive ready to run
When this signal output is valid, it indicates that the drive has no fault, the bus voltage
is normal, and the drive operation prohibition terminal is invalid. In this case, the start
command can be accepted.
16: Drive fault
If the drive fails, an indication is output.
17: Pump increase signal output
Special function for water supply. When the upper limit frequency is reached and the
pump switching condition is met, the pump increase signal is valid.
18: Drive normal running signal (RUN)
When the drive is under normal running status, it outputs an indication signal.
19: Set running time arrival
When the accumulated running time of the drive (U0.37) reaches the set running time
(FC.20), an indication signal is output.
33: Drive forward signal output
34: Drive reversal signal output
35: Cycloid direction of wire drawing machine output
20~32: The output of all functions corresponds to 0~maximum output pulse frequency
of DO2.