EXPERT Standard Series User Manual
232
Read 5#drive’s decelerating time (which is F0.11), and drive response
decelerating time is 6.0S.
Address
Function
Code
Register
Address
Register
Number or
Read bytes
Register
Content
Checksum
0x05
0x03
0x000B
0x0001
None
0xF4C4
0x05
0x03
None
0x02
0x003C
0x4995
Drive’s scaling relationship
A) Frequency’s scaling is 1: 100
To make the drive rotate at 50Hz, the main setting should be 0x1388 (5000).
B) Time’s scaling is 1: 10
To make the drive accelerating time as 30S, the function code should be set to
0x012c (300).
C) Current’s scaling is 1: 10
If the drive’s feedback current is 0x012c, current of this drive is 30A.
D) Output power is an absolute value.
F) Others (i.e. terminal input and output etc.) Please refer to the drive’s user
manual.