EXPERT Standard Series User Manual
182
Figure 6-56 Setting of Protection Action Selection 2
FA.15 defines the protection action selection for abnormal communication, abnormal
contactor and abnormal EEPROM.
Figure 6-57 Setting of Protection Action Selection 1
For example: If system continues running after speed out of tolerance, the thousand
digit is set to 2. If the system continues running without warning when analog input is
abnormal, the thousand digit is set to 8; if the system continues running without warning
when the speed is out of tolerance and the analog input is abnormal, the thousand digit is
set to 2+8=10.
Note: Please select the protection action with caution, and make sure to select
correctly after the fault cause is confirmed, otherwise it may cause expansion of accident
scope, personal injuries or property damages.