EXPERT Standard Series User Manual
172
Figure 6-49 PLC Continuous Cycle Mode
Ten digit: Mode selection for restart after PLC interrupt operation
0: Start running from the first stage
Stop during operation (caused by stop command, fault or power failure), and start
from the first stage after restart.
1: Continue running from the stage frequency of interruption
Stop during operation (caused by stop command or fault), the drive automatically
records the run time of the current stage, and automatically enters this stage after
restarting, and continues the operation in the remaining time at the frequency defined
by this stage, as shown in Figure 6-50.
a1: Stage 1 acceleration time a2: Stage 2 acceleration time
a3: Stage 3 acceleration time d2: Stage 2 deceleration time
f1: Stage 1 frequency f2: Stage 2 frequency
f3: Stage 3 frequency
Figure 6-50 PLC Start Mode 1