EXPERT Standard Series User Manual
102
F1.07
Operating frequency digital
setting
Lower
limit
frequency~upper
limit
frequency
50.00Hz
When the frequency source is selected as digital setting (F1.02=0, 1, 2), the set value
of F1.07 is directly set as the current set frequency of the drive every time the drive is
powered on. The operating frequency digital setting is restricted between upper limit
frequency and lower limit frequency.
F1.08
Model selection
0~1
0
0: G type (universal type)
1: P type (load type of fan and pump)
F1.09
Upper limit frequency
Lower limit frequency ~
maximum frequency
50.00Hz
F1.10
Lower limit frequency
0.00 ~ Upper
limit
frequency
0.00Hz
The upper limit frequency is used to set the upper limit of the output frequency, as
shown in f3 in the following figure. The lower limit frequency is used to set the lower limit of
the output frequency, as shown in f1 in the following figure. The basic operating frequency
f2 is the minimum value of the output frequency when the drive outputs the maximum
voltage. f4 is the maximum frequency. Vmax in the following figure is the maximum output
voltage of the drive.