EXPERT Standard Series User Manual
143
Table 6-12 Output Terminal Function Selection Table
Conte
nts
Corresponding function
Conte
nts
Corresponding function
0
Drive running signal (RUN)
1
Frequency arrival signal (FAR)
2
Frequency level detection signal
(FDT1)
3
Frequency level detection signal
(FDT2)
4
Overload detection signal (OL)
5
Undervoltage lockout stopping
(LU)
6
External fault stop (EXT)
7
Frequency upper limit (FHL)
8
Frequency lower limit (FLL)
9
Drive running at zero speed
10
Simple PLC phase running
completion indication
11
PLC cycle completion indication
12
Set count value arrival
13
Specified count value arrival
14
Set length arrival indication
15
Drive ready to run (RDY)
16
Drive fault
17
Pump increase signal output
18
Drive normal running signal (no
output for jog)
19
Set cumulative running time arrival
20
Output frequency (0~maximum
operation frequency)
21
Reserved
22
Set frequency (0~maximum
operation frequency)
23
Output current (0~2*Iei)
24
Output current (0~2*Iem)
25
Output torque (0 ~ 2*Tem)
26
Output voltage (0~1.2*Ve)
27
Bus voltage (0~800V)
28
AI1 (0~10V/0~20mA)
29
AI2 (0~10V/0~20mA)
30
Output power (0~2*Pe)
31
Upper computer percentage
(0~1000)
32
Expansion card AI3 (-10~10V)
33
Drive forward signal
34
Drive reversal signal
35
Cycloid direction of wire drawing
machine
The functions listed in Table 6-11 are introduced as follows:
0: Drive running signal (RUN)
The drive is under the running status and outputs an indication signal.