Cable Routing
Over time, liquid contaminants such as oil and cleaning solutions will run down the
cables and into any exposed connectors. To minimize the introduction of contaminants
to the connector, route the cables so that there is a loop in the cable just prior to its
attachment to the connector.
Two examples are shown below, depending on the orientation of the connectors. Units
mounted in such a way that the connectors are on the bottom surface of the actuator
require no looping.
In order to avoid the risk of crosstalk between power and signal cables it is recommended that
the power cable be segregated from the I/O and communications cables as much as possible.
Where power and signal cable proximity is required keep their parallel run distance to a
minimum and cross cables at right angles.