Tritex 1 Installation and Setup
110
09/27/12
PN: 27666
Exlar Corporation
Rev. M
952-500-6200M
Digital Jog Mode
Selecting Digital Jog Mode allow the valve to be manually jogged to its closed and open
positions. Click on the Digital Jog Mode button to enable this feature.
Note: The analog signal will be disabled while in digital mode
To close the valve, select the Jog to Closed Position button and hold it down with your mouse
until the desired position is reached. You may then select Teach Closed Position to
automatically fill in the closed valve position parameter. To open the valve, hold down the Jog to
Open Position button until you have reach the desired position. Select the Teach Open Position
to automatically fill in the open valve position parameter.
Note: Unselect Digital Jog Mode to re-enable the analog signal.
Home Operation
Home page
Before normal motion of the actuator can begin, the Tritex must know the actual absolute
position of the actuator. For valve applications, home will be at one end of the stroke or the
other.
Home parameters
Home Position:
To home the actuator in
the valve open position (common) enter
the parameter entered on the Valve
Configuration page under Open Valve.
Velocity Limit:
The Home move maximum
velocity.
Acceleration:
The acceleration and
deceleration ramps that will used during a
home move
Current Limit:
This sets the current limit for
the Home move. If the Termination is set
to Current Limit, the Home move will end