Multi-Function Control ETMFC610
http://www.entecene.co.kr
77
EN
HANCED
TEC
HNOLOGY
7.1.3.2. Operation Count
Place the curser on “OPERATION COUN” in MONITORING menu, press [ENT] button to move
into this menu. Switch (or CB) operation counter and monitoring elements are set in this menu.
GLOBAL SETTING / GENERAL
/
MONITORING / OPERATION COUNT / Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Select whether to use switch operation count monitoring.
If function is activated and operation counter is over “Alarm Count”,
Logic bit DIGOPRC(Diagnostic Operation Count) is set. Logic bit can
be used for Output or Alarm through Interface software.
Figure 7-2. DIGOPRC Diagram
GLOBAL SETTING / GENERAL
/
MONITORING / OPERATION COUNT / Alarm Count
Range
1 ~ 20000
Default
10000
Step
1
Set a number to alarm when Switch (or CB) operation number meets
this set.
[OPERATION COUNT]
>Function: DISABLE
Alarm Count: 10000
Reset Count: 0
[DISABLE, ENABLE]
[OPERATION COUNT]
>
Function: DISABLE
>Alarm Count: 10000
Reset Count: 0
[1~20000:1]