Multi-Function Control ETMFC610
http://www.entecene.co.kr
285
EN
HANCED
TEC
HNOLOGY
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Min. Volt
Range
0.00~1.40 xVT
Default
0.10
Step
0.01 xVT
Set the minimum voltage in order to operate frequency decay element.
Even if one of the three phases on source side is bigger than this setting
value, it will be operated.
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Min. I
Range
0(OFF), 1~630A
Default
60
Step
1A
Set the minimum current in order to operate frequency decay element.
Even if one of the three phases on source side is bigger than this setting
value, it will be operated.
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Reset Time
Range
INCREASE, DECREASE, ABSOLUTE
Default
ABSOLUTE
Step
~
Set operation trend type of Frequency decay element.
When INCREASE is configured,
it operates when frequency decay
rate is increased.
When DECREASE is configured,
it operates when frequency decay
rate is decreased.
When ABSOLUTE is configured,
it operates when absolute value of
frequency decay rate is bigger than pickup setting value.
[FREQUENCY DECAY]
Pickup(Hz/sec):1.00
Time Delay: 2.00
Reset Time: 2.00
Min.Freq: 45.00
>Min.Volt: 0.10
[0.00~1.40:0.01 xVT]
[FREQUENCY DECAY]
>Min.I: 60
Type : ABSOLUTE
[0(OFF), 1~630A:1A]
[FREQUENCY DECAY]
Min.I: 60
>Type : ABSOLUTE
[INC/DEC/ABSOLUTE]