Multi-Function Control ETMFC610
http://www.entecene.co.kr
97
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / TIE VRS
Range
VS, VL, VS&VL
Default
VS
Step
1
Tie VRS (Tie Point Switch Voltage Response Side) : Setting menu for
Tie Point Switch.
“Tie Operate Cnt”
is operated due to Dead line voltage in selected
direction.
VS :
Switch’s Source Side(A,B,C phase) Voltage
VL :
Switch’s Load Side(R,S,T phase) Voltage
VS&VL :
Loop control operates one of either Source side or load
side voltage becomes dead line voltage
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / TIE Operate Cnt
Range
1~5
Default
2
Step
1
Set the close operation count of Tie Point Switch.
Source and Load side are Live Voltage status. When one of the sides
becomes Dead line Voltage, it counts 1, and it repeats once again, it
accumulates the count for 2.
The counter reaches a set value,
“TIE Close TD”
Timer is operated.
The counter is over the set value,
“TIE Close TD”
Timer is reset and
not operated.
The counter is reset by
“TIE Reset TD”
Timer or manual trip.
Dead line Voltage can be determined after
“TIE DL-VS TD”
or
“TIE DL-VL TD”
Timer is finished.
GLOBAL SETTING / GENERAL
/
LOOP CONTROL / TIE Close TD
Range
0.00~600.00
Default
30.00
Step
0.01
Set the close time delay of the Tie Point Switch.
The timer is operated due to
“TIE Operate Cnt”
, and after a set
time, Tie Point Switch is closed.
During the counting, if Source and Load side become Live line
Voltage or Dead line Voltage, the timer is reset. And when the
counter is over a set value of
“TIE Operate Cnt”
, the timer is reset.
DV is determined after
“TIE DL-VS TD”
or
“TIE DL-VL TD”
Timer is finished.
[AUTO SECTION]
>TIE VRS: VS
TIE Operate Cnt: 2
TIE Close TD: 30.00
TIE Open TD: 10.00
TIE Reset TD: 10.00
[VS/VL/VS&VL]
[AUTO SECTION]
>
TIE VRS: VS
>TIE Operate Cnt: 2
>
TIE Close TD: 30.00
TIE Open TD: 10.00
TIE Reset TD: 10.00
[1~5:1]
[AUTO SECTION]
>TIE Close TD: 30.00
TIE Open TD: 10.00
TIE Reset TD: 10.00
TIE DL-VS TD: 1.00
TIE DL-VL TD: 1.00
[0.00~600.00:0.01 s]