Multi-Function Control ETMFC610
http://www.entecene.co.kr
284
EN
HANCED
TEC
HNOLOGY
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Time Delay
Range
0.05~600.00sec
Default
2.00
Step
0.01sec
Set the delay time for frequency decay elements. According to pickup
setting value, time window of frequency decay rate is changed
described in following table.
Detection time of frequency decay element is like below;
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Reset Time
Range
0.05~600.00sec
Default
2.00
Step
0.01sec
Set the reset time of Frequency decay element pickup. It must
configure reset time longer than time window.
GROUP # / MONITORING / FREQUENCY /FREQUENCY DECAY / Min. Freq
Range
45.00~65.00 Hz
Default
50.00
Step
0.01 Hz
Set the minimum frequency in order to operate frequency decay
element. When frequency is bigger than setting value, it will be
operated.
[FREQUENCY DECAY]
Function: DISABLE
Pickup(Hz/sec):1.00
>Time Delay: 2.00
Reset Time: 2.00
Min.Freq: 45.00
[0.05~600.00:0.01s]
[FREQUENCY DECAY]
Function: DISABLE
Pickup(Hz/sec):1.00
Time Delay: 2.00
>Reset Time: 2.00
Min.Freq: 45.00
[0.05~600.00:0.01s]
[FREQUENCY DECAY]
Function: DISABLE
Pickup(Hz/sec):1.00
Time Delay: 2.00
Reset Time: 2.00
>Min.Freq: 50.00
[45.00~65.00:0.01Hz]