Multi-Function Control ETMFC610
http://www.entecene.co.kr
139
EN
HANCED
TEC
HNOLOGY
7.2.1.2. IEC60870-5 Protocol Setup
1) IEC60870-5-101
Move to
“MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PROTOCOL/ IEC60870-
5/ IEC60870-5-101”
to select setting for IEC60870-5-101.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ Function
Range
DISABLE, ENABLE
Default
DISABLE
Step
~
Set whether IEC60870-5-101 protocol is used for communication.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ COM Port
Range
RS232-1, RS232-2, RS485
Default
RS232-1
Step
~
Select a port to use IEC60870-5-101 communication.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ Link Address
Range
1 ~ 65535
Default
1
Step
1
Enter the slave(ETMFC610) address for IEC60870-5-101 comm-
unication.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOLS / IEC60870-5/ IEC60870-5-101/ ASDU Addr
Range
0~65535
Default
0
Step
1
Select the Application Service Data Unit Address.
[IEC870-5-101]
>Function: DISABLE
Port Select:RS232-1
Link Address 1
ASDU Address 0
Cyclic Period 60
[DISABLE/ENABLE]
[IEC870-5-101]
>
Function: DISABLE
>Port Select:RS232-1
Link Address: 1
ASDU Address: 0
Cyclic Period: 60
[PORT1-PORT3]
[IEC870-5-101]
>
Function: DISABLE
>
Port Select:RS232-1
>Link Address: 1
ASDU Address: 0
Cyclic Period: 60
[1~65535:1]
[IEC60870-5-101]
Function: DISABLE
Port Select:RS232-1
Link Address: 1
>ASDU Address: 0
Cyclic Period: 60
[1~65535:1]