Multi-Function Control ETMFC610
http://www.entecene.co.kr
63
EN
HANCED
TEC
HNOLOGY
6.3.2. Main Menu
In the initial screen, press
[FUN]
button, it is moved into Main menu. If press
[FUN] or [ESC]
button in main menu, it is moved to the initial menu. Main menu has sub-menu as below.
MAIN MENU
Main Menu consists of 7 sub-menus.
You can choose any sub-menu by using
[
▲
] [
▼
]
key.
Press
[ENT]
key to select the sub-menu.
As above explanation, you can move and select sub-menu.
6.3.3. Setting Example
Step to change Phase Pickup current of FAULT INDICATION menu in Group1~6 setting.
Move to
“MAIN MENU/ GROUP SETTING/ GROUP #/ BASIC FUNCTION / FI PICKUP
CURRENT”
.
A following screen is displayed.
MAIN MENU/ GROUP #/ BASIC FUNCTION / FI PICKUP CURRENT
Range
0(OFF), 10 ~ 1600A
Default
500A
Step
1A
FI phase pickup current. This value is primary current.
Primary and secondary current is related CT ratio.
(Primary current) = (Secondary current)
×
(CT ratio)
As above example screen, to move to Phase, use
[
▲
] [
▼
]
key and press
[ENT]
key to move into
value column.
Use
[
▲
] [
▼
]
keys and
[
◀
] [
▶
]
keys to change a new value.
Press
[ENT]
key, then you see the changed Phase value.
NOTE :
You must save all changed values at ”Setting Save” menu.
[MAIN MENU]
>1.GLOBAL SETTING
2.GROUP SETTING
3.EVENT
4.MAINTENANCE
5.TIME
6.STATUS
7.METERING
[FI PICKUP CURRENT]
>Phase: 500
Ground: 250
SEF: OFF
Neg Seq’: OFF
[0(OFF), 10~1600:1A]