Multi-Function Control ETMFC610
http://www.entecene.co.kr
123
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING / GENERAL / DEVICE / H/W OPTION / EXT. Temper’ Use
Range
OFF, ON
Default
OFF
Step
~
Select whether the external temperature is installed.
7.1.7.4. Manual Close
Place the curser on “MANUAL CLOSE” in DEVICE menu, press [ENT] button to move in this
menu.
GLOBAL SETTING / GENERAL / DEVICE / MANUAL CLOSE / Time Delay
Range
0.00 ~ 600.00 sec
Default
0.00
Step
0.01 sec
Using the CLOSE button on the front panel, set the closing delay time
to be applied to the main body when the close control is performed in
the field.
When OPEN button is pressed during close delay time, the delay timer
will stop and close operation will not be performed.
If the CLOSE button is pressed again during the close delay time, the
close operation is immediately done even if the delay time remains.
[H/W OPTION]
>
SCADA I/O Use: ON
>
IRIG Use: OFF
>
Wifi Use: OFF
>EXT.Temper’ Use: ON
[OFF/ON]]
[MANUAL CLOSE]
>Time Delay: 0.00
[0.00~600.00:0.01 s]