Multi-Function Control ETMFC610
http://www.entecene.co.kr
182
EN
HANCED
TEC
HNOLOGY
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / Time Tag Type
Range
LOCAL,GMT
Default
LOCAL
Step
~
Set the time type for occurred events in Communication.
NOTE :
This setting is set to be UTC and the setting values associated
with GMT(in “TIME ZONE” menu) are set up incorrectly, the
time of event transmitted is not correct.
GLOBAL SETTING/ COMMUNICATION/ EVENT&ETC / CI Frz Period
Range
0(OFF), 0~60000m
Default
OFF
Step
1minute
Set freeze period of CI points.
7.2.7. Save Setting
This menu allows you to save the changed settings of the GENERAL menu. The procedure for
storing the set value is described in
“6.3.4. Setting Save”
.
[EVENT&ETC SETUP]
>
AI Evt Method: ALL
>
CI Evt Method: ALL
>
DO Cmd at Local:OFF
>
Time Syn’ Ref:LOCAL
>Time Tag Type:LOCAL
[LOCAL/GMT]
[COMMON]
CI Evt Method: ALL
DO Cmd at Local:OFF
Time Syn’ Ref:LOCAL
Time Tag Type:LOCAL
>CI Frz Period: OFF
[0(OFF),0~60000:1m]