Multi-Function Control ETMFC610
http://www.entecene.co.kr
221
EN
HANCED
TEC
HNOLOGY
GROUP #/ PROTECTION/INRUSH RESTRAINT/ RESTORE MIN. TIME/ RMT TIME
Range
0.01 ~ 600.00 sec
Default
0.60
Step
0.01 sec
Select the restore minimum time required for the inrush current.
The Restore Minimum Time have to raised pickup levels for time
overcurrent detection from inrush duration fault pickup current back to
nominal pickup level.
4) Reset Current & Time Setup
GROUP #/ PROTECTION/ INRUSH RESTRAINT/ INRUSH RES’ RESET / P-Reset I
Range
10~1600A
Default
500
Step
1A
Set the level of reset current for phase inrush restraint.
Inrush current that is lower than this reset current setting level, is kept
for the reset time, Inrush current restraint algorithm is stopped and
normal over current protection function operates.
GROUP #/ PROTECTION/ INRUSH RESTRAINT/ INRUSH RES’ RESET / G-Reset I
Range
10~1600A
Default
250
Step
1A
Set the level of reset current for ground inrush restraint.
GROUP #/ PROTECTION/ INRUSH RESTRAINT/ INRUSH RES’ RESET / S-Reset I
Range
0.1~160.0A
Default
10.0
Step
0.1A
Set the level of reset current for sensitive earth inrush restraint.
[RESTORE MIN. TIME]
P-Function: ENABLE
G-Function: ENABLE
S-Function: ENABLE
Q-Function: ENABLE
>RMT TIME: 0.60
[0.01~600.00:0.01 s]
[INRUSH RES’ RESET]
>P-Reset I: 500
G-Reset I: 250
S-Reset I: 10.0
Q-Reset I: 500
Reset Time: 0.60
[10~1600:1 A]
[INRUSH RES’ RESET]
>
P-Reset I: 500
>G-Reset I: 250
S-Reset I: 10.0
Q-Reset I: 500
Reset Time: 0.60
[10~1600:1 A]
[INRUSH RES’ RESET]
>
P-Reset I: 500
G-Reset I: 250
>S-Reset I: 10.0
Q-Reset I: 500
Reset Time: 0.60
[10~1600:1 A]