8.5.9. Live Line Block
It is to block LBS closing if the load side is live line.
GROUP # / MONITORING /LIVE LINE BLOCK / Function
Range
DISABLE, ENABLE
Default
OFF
Step
~
It decides whether to use Live line block.
GROUP # / MONITORING / LIVE LINE BLOCK / Live Level
Range
0.10~1.40 xVT
Default
0.80
Step
0.01 xVT
Set pickup level of live line
GROUP # / MONITORING / LIVE LINE BLOCK / Source
Range
VS, VL, VS&VL
Default
VS&VL
Step
~
Set which side of voltage to detect live line.
VS :
Switch(or CB)’s Source Side(A,B,C phase) Voltage
VL :
Switch(or CB)’s Load Side(R,S,T phase) Voltage
VS&VL :
Switch(or CB)’s Source and Load Side Voltage
GROUP # / MONITORING /LIVE/DEAD BLOCK / Time Delay
Range
0.00~600.00 sec
Default
0.10
Step
0.01sec
Set a time to detect live line in load side. The live line is determined if
load side voltage is more than pickup level for this set time.
[LIVE LOAD BLOCKING]
>Funcktion: DISABLE
>
Live Level: 0.80
>
Source: VS&VL
Time Delay: 0.10
[DISABLE/ENABLE]
[LIVE LOAD BLOCKING]
Funcktion: DISABLE
>Live Level: 0.80
>
Source: VS&VL
Time Delay: 0.10
[0.10~1.40:0.01 xVT]
[LIVE LOAD BLOCKING]
Funcktion: DISABLE
>
Live Level: 0.80
>Source: VS&VL
Time Delay: 0.10
[VS/VL/VS&VL]
[LIVE LOAD BLOCKING]
Funcktion: DISABLE
>
Live Level: 0.80
Source: VS&VL
>Time Delay: 0.10
[0.00~600.00:0.01s]