GLOBAL SETTING / GENERAL
/
EVENT RECORDER / Wave Pre-Cycle
Range
1 ~ 20 cycle
Default
5
Step
1 cycle
Pre-cycle is to record (capture) a number of wave cycle before trigger
occurring. Pre-cycle changes depending on sampling ratio. For
instance, if pre-cycle is set for 5 cycle, when sampling number is 64, 5
cycle is applied, the sampling number is 32, pre-cycle is 10, 16 case, 20
pre-cycle is applied.
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / Wave P/S
Range
P(1ST), S(2ND)
Default
P(1ST)
Step
~
Select if analog data value is primary data or secondary data recorded
on Wave cycle. Record the current and voltage data applied to setting
value ETMFC610 on secondary side (the CT ratio and VT ratio divided
by the primary side data).
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / L&E Record
Range
OFF, ON
Default
OFF
Step
~
Set whether Load&Energy event is recorded or not.
GLOBAL SETTING / GENERAL
/
EVENT RECORDER / L&E Interval
Range
5, 10, 15, 20, 30, 60
Default
15
Step
~
Set the interval to record Load&Energy events.
[EVENT RECORDER]
>
Wave Recorder: OFF
>
Wave S/R: 64
>Wave Pre-Cycle: 5
Wave P/S: P(1ST)
L&E Record: ON
[1~20:1cycle]
[EVENT RECORDER]
>
Wave Recorder: OFF
>
Wave S/R: 64
>
Wave Pre-Cycle: 5
>Wave P/S: P(1ST)
L&E Record: ON
[P(1ST)/S(2ND)]
[EVENT RECORDER]
>L&E Record: OFF
L&E Interval: 15
COMTRADE Record:OFF
COMTRADE Rev.: 1999
>
COMTRADE P/S:P(1ST)
[OFF/ON]
[EVENT RECORDER]
>
L&E Record: OFF
>L&E Interval: 15
COMTRADE Record:OFF
COMTRADE Rev.: 1999
>
COMTRADE P/S:P(1ST)
[5/10/15/20/30/60]