Multi-Function Control ETMFC610
http://www.entecene.co.kr
355
EN
HANCED
TEC
HNOLOGY
Table 14-1. Warning Events(2/3)
EVENT
EVENT TEXT
(LCD)
EXPLANATION
ETMFC610
ACTION
USER’ RECOMMENDED ACTION
SETTING
(Refer to SET
CHANGE
Event)
GLSCHG
(Global setting)
and GRSCH1~
GRSCH6(Group
setting)
Setting Changed
-
No problem
* But somebody modified the setting
data.
TRIP
& CLOSE
CF
Close fail
-
1. Check the close/trip module
2. Check the receptacle pin
3.Ensure Control cable is securely
connected
4.Check SMPS-C module
5.Check close/open magnetic contactor
(MC)
TRF
Trip fail
-
DIGOPOW
Capacitor charger power
supply error
-
1.Ensure status input connector cable is
securely connected
2.
Check SMPS-C module
3. Check IN210 status
DIGIGBT
IGBT error
-
1.Ensure status input cable is securely
connected
2. Check IN210 and IN211stauts
DIGCLC
Close coil error
-
1.Ensure status input cable is securely
connected
2. Check IN210, IN212, IN213 and
IN214 status
DIGTRC
Trip coil error
-
1.Ensure status input cable is securely
connected
2. Check IN210 and IN213stauts
SELF TEST
SELFTER
System error detected
while booting
Detail
message
are
recorded in diagnostic
event
1.Check the diagnostic event
2.Refer to EVENT TEXT
DIGGLSET
Global setting error
Restored default setting
by itself
1. Execute System Restart
2. Execute default setting
3. Replace Main Processing Module
DIGGRSET
Group setting error
Restored default setting
by itself
1. Execute System Restart
2. Execute default setting
3. Replace Main Processing Module
DIGSPU
DSP module error or
ADC processer error
Correct
measurement
and protection does not
work
1. Execute System Restart
2. Replace DSP Module
3. Replace Main Processing Module
DIGADC
A/D conversion error
Correct
measurement
and protection does not
work
1. Execute System Restart
2. Replace DSP Module
3. Replace Main Processing Module
DIGEVT
Recorded events format
error
Cleared events by itself
1. Execute All Clear Event
2. Execute System Restart
3. Replace Main Processing Module
DIGCNT
Registered count data
error
Cleared count by itself
1. Execute All Clear Data
2. Execute System Restart
3. Replace Main Processing Module
DIGMEM
Registered data error
Cleared
data(energy,
max. demand, contact
wear
and
battery
capacity) by itself
1. Execute All Clear Data
2. Execute System Restart
3. Replace Main Processing Module