Multi-Function Control ETMFC610
http://www.entecene.co.kr
354
EN
HANCED
TEC
HNOLOGY
14. MAINTANANCE
14.1. Warning Events
ETMFC610 possesses self-test and self-diagnostic function. If any abnormal behavior is detected in
the system, it records the corresponding events in the Diagnostic Event or System Event and
transmits it to SCADA system via remote.
“
Table 14-1. Warning Events”
is the list of self-diagnosis conditions managed by ETMFC610
system processing method and user’s recommended actions
.
. Users are requested to refer to
“Table
14-1. Warning Events”
in case of any abnormality in the system.
Table 14-1. Warning Events(1/3)
EVENT
EVENT TEXT
(LCD)
EXPLANATION
ETMFC610
ACTION
USER’ RECOMMENDED
ACTION
SYSTEM POWER
ACFAIL
External power FAIL
‘AC SUPPLY’
LED OFF
1. Check AC Power NFB
2. Check AC Power fuse
3. Check AC supply, ensure AC -
connector is securely connected
CHGBAD
Battery charge circuit FAIL
; CHGLOW or CHGHIGH
‘CHARGER’
LED OFF
1. Check AC supply
2. Check Battery charge Voltage
(range DC 27 ~ DC 28V)
3. Replace Analog Module
1)
CHGLOW
Battery charge circuit volt
LOW (Value 25V)
2)
CHGHIGH
Battery charge circuit volt
HIGH (Value
≥
28V)
BATBAD
Battery BAD
; BATLOW, BATHIG,
NOBAT or
Batt Cap’ Alarm Level
when BATT Management
is ENABLED.
‘BATTERY’
LED OFF
1. Check AC Power NFB
2. Check AC Power fuse
3. Check AC supply, ensure AC
connector is securely connected
4. Replace Battery charge T.R
5. Check battery NFB
6. Check battery connection
1)
BATLOW
Battery volt LOW
(15V < Value 21V)
2)
BATHIGH
Battery charge circuit volt
HIGH (Value
≥
28V)
3)
NOBATT
NO Battery (Value < 15V)
POWER
DOWN
MODE
PWDOWN
Power down mode
(Value < 21V and ACFAIL)
Controller
power turn off
No problem
1. Check AC supply
2. Check battery
GAS STATUS
*. applied only gas
insulation type
(EVR)
GASLOW
Gas pressure LOW
(Value 0.1 bar)
CLOSE block
When ‘Opr’ Block
GPF’ setting is
ON
1.Ensure Control cable is securely
connected
2. Check Control cable fault
3. Replace Main Processing Module
4. Replace body.
GASHIGH
Gas pressure HIGH
(Value
≥
1.5V)
SYSTEM
RESTART
SYSRST
System restarted
-
No problem
CLDRST
Cold Restarted
-
No problem