Promag 50
Wiring
Hauser
49
4.1.2
Cable specifications
Signal cable
• 3 × 0.38 mm² PVC cable with common, braided copper shield (
7 mm) and individually
shielded cores
• With Empty Pipe Detection (EPD): 4 × 0.38 mm² PVC cable with common, braided copper shield
(
7 mm) and individually shielded cores
• Conductor resistance:
50
km
• Capacitance: core/shield:
420 pF/m
• Permanent operating temperature: –20 to +80 °C
• Cable cross-section: max. 2.5 mm²
Coil cable
• 2 × 0.75 mm² PVC cable with common, braided copper shield (
7 mm)
• Conductor resistance:
37
km
• Capacitance: core/core, shield grounded:
120 pF/m
• Operating temperature: –20 to +80 °C
• Cable cross-section: max. 2.5 mm²
• Test voltage for cable insulation:
1433 V AC r.m.s. 50/60 Hz or
2026 V DC
A0003194
Fig. 33:
Cable cross-section
a
Signal cable
b
Coil current cable
1
Core
2
Core insulation
3
Core shield
4
Core jacket
5
Core reinforcement
6
Cable shield
7
Outer jacket
Reinforced connecting cables
As an option, Hauser can also deliver reinforced connecting cables with an additional,
reinforcing metal braid. Reinforced connecting cables should be used when laying the cable directly
in the ground, if there is a risk of damage from rodents or if using the measuring device below IP 68
degree of protection.
Operation in zones of severe electrical interference:
The measuring device complies with the general safety requirements in accordance with EN 61010
and the EMC requirements of IEC/EN 61326.
"
Caution!
Grounding is by means of the ground terminals provided for the purpose inside the connection
housing. Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as
short as possible.