Promag 50
Wiring
Hauser
47
Cable termination for the remote version
Promag D / Promag L / Promag W / Promag P
Terminate the signal and coil current cables as shown in the figure below (Detail A).
Ferrules must be provided on the fine-wire cores (Detail B:
m
= red ferrules,
1.0 mm;
n
= white ferrules,
0.5 mm).
* Stripping only for reinforced cables
"
Caution!
When fitting the connectors, pay attention to the following points:
•
Signal cable
Make sure that the ferrules do not touch the wire shield on the sensor side.
Minimum distance = 1 mm (exception "GND" = green cable)
•
Coil current cable
Insulate one core of the three-core wire at the level of the core reinforcement; you only require two cores for the connection.
TRANSMITTER
Signal cable
Coil current cable
A0002687
A0002688
SENSOR
Signal cable
Coil current cable
A0002646
A0002650
A
B
GND
m
m
m
m
n
n
n
n
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
100 (3.94)*
mm (inch)
A
B
m
m
m
90 (3.54)*
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
mm (inch)
A
B
m
n
m
n
n
GND
mm (inch)
80 (3.15)
50 (1.97)
8 (0.31)
³
1 (0.04)
170 (6.69)*
20 (0.79)*
17 (0.67)
B
A
m
m
m
mm (inch)
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
160 (6.30)*
20 (0.79)*