Promag 50
Installation
Hauser
41
3.3.8
Installing the wall-mount housing
There are various ways of installing the wall-mount transmitter housing:
• Direct wall mounting
• Installation in control panel (with separate mounting kit, accessories)
• Pipe mounting (with separate mounting kit, accessories)
"
Caution!
• Make sure that the ambient temperature does not exceed the permissible range at the mounting
location, –20 to +60 °C (–4 to + °140 F), optional –40 to +60 °C (–40 to +140 °F). Install the
device at a shady location. Avoid direct sunlight.
• Always install the wall-mount housing in such a way that the cable entries are pointing down.
Direct wall mounting
1.
Drill the holes as illustrated in the graphic.
2.
Remove the cover of the connection compartment (a).
3.
Push the two securing screws (b) through the appropriate bores (c) in the housing.
– Securing screws (M6): max. Ø 6.5 mm (0.26")
– Screw head: max. Ø 10.5 mm (0.41")
4.
Secure the transmitter housing to the wall as indicated.
5.
Screw the cover of the connection compartment (a) firmly onto the housing.
a0001130
Fig. 27:
Mounted directly on the wall
a
b
c
c
90 (3.54)
35 (1.38)
192 (7.56)
81
.5(
3
.2)
mm (inch)