7.6.8 Functional Examples of Start/
Stop Transitions
Starting an additional pump
This figure shows a possible sequence with all levels and
functions involved when a additional pump is started by
means of the pump control relays. The starting of the
second pump is controlled by one of the relay outputs. The
relay in this example starts the pump directly on line. Of
course other start/stop equipment, like a soft starter, could
be controlled by the relay output.
Fig. 87 Time sequence starting an additional pump.
Flow
Set view ref. [310]
Feedback Flow
time
Master pump
Max speed
Speed
Transition Speed Start
Min speed
Lower band
Upper band
Start delay [399]
Settle time start [39D]
Start ramp depends
on start method
Start command
Speed
2nd pump
time
time
[39E]
[343]
[341]
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......