CG Drives & Automation 01-7491-01r0
Control Connections
49
4.2.1 Stand by supply interface
(SBS)
The control board mounted standby supply, X11 connector,
provides the possibility of keeping the communication
system up and running without having the 3-phase mains
connected. Another advantage is that the system can be set
up without mains power. The option will also give backup
for communication failure if main power is lost.
The standby supply should be supplied with a 24 VDC
±10% double isolated transformer capable of supplying 1A
continues current. Recommended fuse is 2A. Cable length
limited to 30 m. If the cable is longer than 30 m, a shielded
cable must be used.
4.3
Configuration with
jumpers and switches
4.3.1 Analogue input configuration
(S1 - S4)
The jumpers selections S1 to S4 are used to set the input
configuration for the 4 analogue inputs AnIn1, AnIn2,
AnIn3 and AnIn4 as described in table 23. See fig. 56 for the
location of the jumpers.
Table 22 X11 terminal
Terminal
Name
Function
1
+
24 VDC
±
10%
2
-
0 V
NOTE: In case the isolated DC measurement board
(that incorporate stand by supply [SBS] functionality)
the control-board SBS should not be used. Rather
the SBS on the isolated DC measurement board
should be used. Failure to comply with this will break
DC-link voltage measurement.
Table 23
Settings selectors S1-S4
Input
Signal type
Selector
configuration
AnIn1
Voltage
S1
Current (default)
S1
AnIn2
Voltage
S2
Current (default)
S2
AnIn3
Voltage
S3
Current (default)
S3
AnIn4
Voltage
S4
Current (default)
S4
NOTE: Scaling and offset of AnIn1 - AnIn4 can be
configured using the software. See menus [512],
[515], [518] and [51B] in section 11.5, page 152.
NOTE: the 2 analogue outputs AnOut 1 and AnOut 2
can be configured using the software. See menu [530]
section 11.5.3, page 158
U
I
U
I
U
I
U
I
U
I
U
I
U
I
U
I
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......