Installation
CG Drives & Automation 01-7491-01r0
3.1.2 Remove/open the lower front
cover on Frame size E2, F2
and FA2 (IP20/21)
Fig. 30 Loosen the two screws and remove the lower cover
(principle drawing).
In order to access the mains, motor, DC+/DC- and brake
terminals, remove the lower cover in following order
•
Loosen the two screws B (see fig. 30).
•
Pull down the cover a bit and lift it away.
3.2
Cable connections for
small and medium frame
sizes
IP54 - FDU48/52-003 to 074 (Frame sizes B, C and D)
IP54-FDU69-002 to 058 (Frame sizes C69 and D69)
IP20/21 - FDU48-025 to 365 (Frame sizes C2, D2, E2, F2
and FA2)
IP20/21 - FDU69-002 to 058 (Frame sizes C2(69) and
D2(69))
3.2.1 Mains cables
Dimension the mains and motor cables according to local
regulations. The cable must be able to carry the AC drive
load current.
Recommendations for selecting mains
cables
•
To fulfil EMC purposes it is not necessary to use
screened mains cables.
•
Use heat-resistant cables, +75
°
C (167
°
F) or higher.
•
Dimension the cables and fuses in accordance with local
regulations and the nominal input current of the drive
See table 65, page 221.
•
PE conductor cross-sectional area shall for phase cable
size < 16 mm
2
(6 AWG) be >10 mm2 Cu (16 mm
2
Al)
or a second PE conductor with same area as original PE
conductor,
for cable size above 16mm
2
(6 AWG) but smaller or
equal to 35mm
2
(2 AWG) the PE conductor cross-sec-
tional area shall be at least 16mm
2
(6 AWG).
For cables >35mm
2
(>2 AWG) the PE conductor cross-
sectional area should be at least 50% of the used phase
conductor.
When the PE conductor in the used cable type is not in
accordance with the above mentioned cross-sectional
area requirements, a separate PE conductor should be
used to establish this.
•
The litz ground connection see fig. 42, is only necessary
if the mounting plate is painted. All the AC drives have
an unpainted back side and are therefore suitable for
mounting on an unpainted mounting plate.
Connect the mains cables according to fig. 31 to 39. The
AC drive has as standard a built-in RFI mains filter that
complies with category C3 which suits the Second
Environment standard.
B
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......